OMM 1008-1
59
VIEW UNIT WATER
°
°
°
°
F(3)
Water Flow Rates
Evap = XXXXX GPM
Cond = XXXXX GPM
View Refrigerant Status
VIEW UNIT REFRG (1)
psi
°
°
°
°
F
Sat Evap XXX.X XX.X
Sat Cond XXX.X XX.X
VIEW UNIT REFRG (2)
Suct Line = XXX.X
°
°
°
°
F
Liquid Line= XXX.X
°
°
°
°
F
Lift Press =XXXX psi
View Tower Status
To w e r C o n t ro l = Te mp / N o n e
To w e r C o n t ro l = L i f t
VIEW UNIT TOWER (1) VIEW UNIT TOWER (1)
Stages ON = 2 of 4
Stages ON = 2 of 4
Setpoint = XXX
°
°
°
°
F Setpoint = XXXX psi
The first Stages ON value is the number of fan stages ON. The second number is the Tower Stages setpoint
(0 if Tower Control = None).
VIEW UNIT TOWER (2)
Bypass Valve = XXX%
VFD Speed = XXX%
The Bypass Valve value is “None” (in place of XXX%) if the Valve/VFD Control setpoint = None or VFD
Stage. The VFD Speed value shall be “None” if the Valve/VFD Control setpoint = None, Valve Setpoint, or
Valve Stage.
View Compressor Status
NOTE
: In the following VIEW COMP screens, the #N field indicates which compressor (#1, or #2,) is being
viewed. There are two columns of menus, the first for compressor #1, the second for #2.
VIEW COMP#N (1)
State = RUN
% RLA = XXX %
Evap LWT =000.0
°
°
°
°
F
State settings can be OFF, START, INTLOK, HOLD, LOAD, UNLOAD, SHUTDOWN, STOP, and ALARM
as determined from the Comp State variable, the Load and Unload outputs, and the presence of a compressor
shutdown alarm.