OMM 1008-1
35
Figure 12, View Menu
This View Menu is accessed by pressing the MENU button from the Detail View Screen. The menu screen
accesses several informational screens as shown in the above figure.
Figure 13, View Compressor State Screen
For example, pressing the Compressor-State button on the Menu
screen in Figure 12 will display the screen shown in Figure 13 on the
right side of both the Menu screen and the Detail View screen. The
Compressor State screen is basically a compilation of the events that
the chiller sequences through at startup. A green light (light gray in
the figure) indicates that a particular sequence requirement has been
satisfied. It is recommended that this screen be viewed during the
start up sequence. One can see the requirements light up as they are
met and quickly see why a non-start may have occurred. For
example, The Evap Flow OK will light when the evaporator flow
switch is closed by flow.
The bottom sections (from "RUN" down) are in effect during the shut
down process. The sequence transitions back to OFF at this point
and the OFF light will be illuminated.