Page 17
Options : (Single digit entry required)
1
Duress reports enabled
0
Duress reports disabled
Options : (Single digit entry required)
1
Auto - isolation enabled
0
Auto - isolation disabled
Description :
Keyboard duress may be disabled to
prevent accidental duress alarms from
private residences.
Note:
Description :
Normally if an attempt to arm the panel
with a faulted section (other than an exit/
entry section) is made the panel will give
an error beep. If this option is enabled
then faulted sections will be automatically
isolated and will be reported as such.
Duress is achieved by adding 1 to the last digit of the user code eg. 1234 becomes 1235, 6789 be-
comes 6780.
Example : While in program mode (Program LED flashing)
Key
Sequence
Operation
74
- Enter
Function
No.
1
-
Enter Option (1 = reports enabled)
On
- Store
Entry
Installer may now exit program mode by pressing the OFF button or continue program-
ming by entering a new function number.
Function 74 - Keyboard Duress On / Off
Default - Duress disabled
Function 75 - Auto-Isolate On/Off
Default - Auto-Isolate disabled
Example : While in program mode (Program LED flashing)
Key
Sequence
Operation
75
- Enter
Function
No.
1
-
Enter Option (1 = auto-isolation enabled)
On
- Store
Entry
Installer may now exit program mode by pressing the OFF button or continue programming by enter-
ing a new function number.
Example : While in program mode (Program LED flashing)
Key
Sequence
Operation
73
- Enter
Function
No.
3
-
Enter Option (3 = 12hrs)
On
- Store
Entry
Installer may now exit program mode by pressing the OFF button or continue
programming by entering a new function number.
Description :
This sets the delay from when program
is exited till the dialler sends its first test
report, in multiples of 4 hours.
Options : (Single digit entry required)
0 to 9 = number of 4 hr periods before the first test
Function 73 - Delay till First test report
Default - 12 hours