![MB 700 H Series Operation Manual Download Page 33](http://html1.mh-extra.com/html/mb/700-h-series/700-h-series_operation-manual_1752089033.webp)
33
created at start of each file
transmission time period.
5
Add Param
Description
Header
Enabled or disabled
If enabled, parameter
description header will be
added to the file
6
Add Param
Statistical
Values
Enabled or disabled
Enabled
: Calculated statistical
values – minimum, maximum,
average, standard deviation, and
integrated value shall be added
to the log (as per parameter
configuration).
Disabled
: Only parameter value
shall be added to the log.
7
Delete File after
Transmission
Enabled or disabled
Enabled
: Data log file shall be
deleted after successful
transmission.
Disabled
: Data log file will not
be deleted after transmission.
8
File Name
Provide required
data log file name
Data log files will be saved with
this name. Time in
‘YYYY_MM_DD_HH_MM’
format will be added to the file
name.
e.g.
‘MBDataLog_2020_03_15_15_
45’
9
File Server URL
URL for the file
server
Data logger shall resolve the
URL to get the file server IP
address.
10
File server IP
IP address for the
file server
11
File server
Username
Username for the
client
12
File server
Password
Password for the
client
FTP client will use the
configured username and
password to connect to the file
server.
13
File Transmit
Time Period
(sec)
Files transmit time in
seconds
Logged file will be transmitted
after this time.
Table-4.7.2.1: Configuration – remote file transfer operation
Notes:
i)
If ‘Modem; is selected media for file transfer, and it fails, file transfer shall be
tried via ETH port (if the link to configured gateway is OK).