Gas Information _______________________

Explosion Hazard

Use a new CSA International approved gas supply
line.

Install a shutoff valve.

Securely tighten all gas connections.

If connected to LP, have a qualified person make sure
gas pressure does not exceed 13” water column.

Examples of a qualified person include:

licensed heating personnel,
authorized gas company personnel, and
authorized service personnel.

Failure to do so can result in death, explosion, or fire.

!

  WARNING

Type of Gas

This dryer is equipped for use with natural gas.  It is design-
certified by CSA International for L.P. (propane and butane)
gases  with appropriate  conversion  (L.P.  kit 887299).  No
attempt  shall be made to convert the dryer  from the gas
specified on the serial/rating plate for  use  with a different
gas without consulting the serving gas supplier.  Conversion
must be done by a qualified service technician.
It  is  your  responsibility to have all  plumbing  connections,
materials, and workmanship  conform to local and state
regulations  or  codes of the country of destination.  In the
absence of such codes, all plumbing connections, materials,
and  workmanship  must  conform to the applicable  local
requirements.  In the USA this is the National Fuel Gas Code
ANSI Z223.1-LATEST EDITION, or in Canada, the Canadian
Installation  Codes  CAN/CGA-B149.1-M91  (Natural Gas)  or
CAN/CGAB149.2-M91 (L.P. Gas) or LATEST EDITION.
It is important that gas pressure regulators meet applicable
pressure requirements, and that gas meters be rated for the
total amount of all the dryer Btu being supplied.
For ease of service, the individual gas  supply  line of each
dryer must have its own manual shutoff valve.
The dryer must be isolated from the gas supply piping system
by  closing  its  individual  manual  shutoff  valve during any
pressure test of the gas  supply  system at test pressures
equal to or less than 1/2 psig (3.5 kPa).
The dryer and its  individual  shutoff  valve  must be
disconnected from the gas supply piping system during any
pressure testing of that system at test pressures  in excess
of 1/2 psig (3.5 kPa).
Failure to isolate or disconnect the dryer from supply as noted
can cause irreparable damage to the gas valve, voiding the
warranty.

*

Consult factory for elevations over 2,000 feet (609.6  meters) for correct
burner orifice size(s).

** Btu rating for both tumblers.

Gas Connections

Inlet  connection ..... 1/2” M.N.P.T. (1 per pocket)
Inlet supply size .... 1/2” Pipe (minimum) (1 per pocket)
Combined top and bottom  require a 3/4”  supply  (minimum)

Piping / Connections

The dryer is provided with two 1/2” N.P.T. inlet pipe connection
at the rear of the dryer.  It is recommended that a gas shutoff
valve be provided to the gas supply line of each pocket for
ease  in  servicing.
The  size of the main gas  supply  line  (header)  will  vary
depending on the distance this  line travels  from the gas
meter.  Specific information regarding supply line size should
be determined by the gas supplier.

NOTE: Undersized gas supply piping can create a low or
inconsistent pressure, which will result in erratic operation
of the burner  ignition  system.

Natural Gas Specifications

**

Nominal

Heating

Value

Supply

Pressure

Gross

Heat Input

Orifice

Size

*

Orifice

(Injector)
Quantity

Burner

Pressure

B tu /ft

3

in WC

Btu/hr

kW

DMS

mm

in WC

1,000

6.0-12.0

144,000

42.2

20

4.089

2

3.5

NOTE: Undersized gas  piping will  result  in  ignition
problems,  slow drying, and increased use of energy.

The input ratings shown on the data label are for elevations
up to 2,000 feet (610 meters), unless elevation requirements
of over 2,000 feet (610 meters) were specified at the time the
dryer order was placed with the factory.  The adjustment or
conversion of dryers in the field for elevations over 2,000 feet
(610 meters) is made by changing each burner orifice.  If this
conversion is necessary, contact the distributor who sold the
dryer or contact the manufacturer.

IMPORTANT: If connection to this dryer is made with a
flexible hose,  it  must be suitable for the appliance
category  in accordance  with national  installation
regulations of the country of destination, and if in doubt the
installer must contact the supplier.  The manufacturer of
this dryer does not recommend the use of flexible gas
supply  line/hose.

Pipe joint compounds that resist the action of natural,
propane, and butane gases  must be used.

In  the  U.S.A.: 

An  individual  manual  shutoff  valve  must be

installed within 6 feet (1.8 meters) of the dryer in accordance
with the National Fuel Gas Code, ANSI Z223.1.

In  Canada:

 An individual  manual  shutoff  valve  must be

installed  in accordance  with the B149.1, Natural Gas and
Propane Installation  Code.  It is  recommended that an
individual manual shutoff valve be installed within 6 feet (1.8
meters) of the dryer.

Summary of Contents for MLG-30PDA

Page 1: ...MLG 30PDA Installation Manual Stack Dryer Part No 113543 3 RETAIN THESE INSTRUCTIONS IN A SAFE PLACE FOR FUTURE REFERENCE...

Page 2: ......

Page 3: ...m rubber or similarly textured rubber like materials Clean lint screen every third load to fourth Keep area around the exhaust opening and adjacent surrounding areas free from the accumulation of lint...

Page 4: ...dryer must be used only for drying water washed fabrics The dryer must never be operated with any of the back guards or service panels removed Personal injury or fire could result The wiring diagram...

Page 5: ...ERS PER 48 53 TRUCK 30 33 VOLTAGE AVAILABLE 120V 1 2w 60 Hz APPROXIMATE NET WEIGHT 675 lb 306 kg APPROXIMATE SHIPPING WEIGHT 710 lb 322 kg AIRFLOW PER POCKET 400 cfm 11 3 cmm HEAT INPUT PER POCKET 72...

Page 6: ...manual refer to Exhaust Requirements section Excessive Weight Hazard Use two or more people and mechanical equipment to lift move and install dryer Failure to do so can result in back or other injury...

Page 7: ...ely is 29 inches 74 cm B A minimum overhead clearance of 12 inches 30 48 cm is required C Dryer should be positioned a minimum of 12 inches 30 48 cm away from the nearest obstruction 24 inches 60 96 c...

Page 8: ...tion regulations of the country of destination Outside Ductwork Protection To protect the outside end of the horizontal ductwork from the weather a 90 elbow bent downward should be installed where the...

Page 9: ...trical Code ANSI NFPA NO 70 LATEST EDITION or in Canada the Canadian Electrical Codes Parts 1 2 CSA C22 1 1990 or LATEST EDITION IMPORTANT Failure to comply with these codes or ordinances and or the r...

Page 10: ...nada Standards Canadian Electrical Codes Parts 1 2 CSAC22 1 1990 or LATEST EDITION The ground connection may be to a proven earth ground at the location service panel Electrical Connections A wiring d...

Page 11: ...feet 609 6 meters for correct burner orifice size s Btu rating for both tumblers Gas Connections Inlet connection 1 2 M N P T 1 per pocket Inlet supply size 1 2 Pipe minimum 1 per pocket Combined top...

Page 12: ...egulator must be installed in the gas supply line header if the natural gas pressure exceeds 13 0 in WC 32 34 mb pressure A minimum 1 8 N P T plugged tap accessible for a pressure gauge connection mus...

Page 13: ...o operate the dryer Read all DANGER WARNING CAUTION and DIRECTION labels attached to the dryer Check incoming supply voltage to be sure that it is the same as indicated on the data label Be sure that...

Page 14: ...rformed by a qualified trained technician service agency or gas supplier If service is required contact the Maytag distributor from whom the equipment was purchased If the distributor cannot be contac...

Page 15: ...ick A back draft damper that is sticking partially closed can result in slow drying and shutdown of heat circuit safety switches or thermostats When cleaning the dryer cabinet s avoid using harsh abra...

Page 16: ...MLG 30PDA Manuel d installation S cheuse superpos e Part No 113543 3 CONSERVER CES INSTRUCTIONS EN LIEU S R POUR R F RENCE ULT RIEURE...

Page 17: ...minimum le risque d incendie ou d explosion ou pour viter tout dommage mat riel toute blessure ou la mort Ne pas entreposer ni utiliser d essence ni d autres vapeurs ou liquides inflammables proximit...

Page 18: ...18 Maytag Co 113543 3...

Page 19: ...NT La s cheuse doit tre utilis e uniquement pour s cher du linge lav l eau La s cheuse ne doit jamais fonctionner alors que les protections arri re ou les panneaux de service sont d mont s Des blessur...

Page 20: ...MATIF 675 lb 306 kg POIDS BRUT APPROXIMATIF TRANSPORT 710 lb 322 kg D BIT D AIR PAR TAMBOUR 400 pi min 11 3 m min PUISSANCE CALORIFIQUE PAR TAMBOUR 72 000 Btu h 18 143 kcal h RACCORD D VACUATION DIAM...

Page 21: ...eter recycler tous les mat riaux d emballage IMPORTANT Il est imp ratif d installer la s cheuse sur un plancher non combustible La s cheuse doit tre utilis e dans un lieu non combustible Avant d insta...

Page 22: ...doit tre am nag e de fa on ce que l air d appoint soit uniform ment r parti entre toutes les s cheuses A 12 pouces 30 48 cm B 24 pouces 60 96 cm EXEMPLE Pour un ensemble de quatre s cheuses deux ouve...

Page 23: ...par dessus Tous les raccords de conduit doivent tre couverts de ruban adh sif pour viter que l humidit et la charpie s chappent dans le local Les trappes d inspection doivent tre install es des point...

Page 24: ...et 2 CSA C22 1 1990ouDERNI RE DITION IMPORTANT Tout manquement ces codes ou r glements et ou aux conditions stipul es dans ce manuel peut provoquer des blessures ou la panne d un organe REMARQUE La p...

Page 25: ...e sur le tableau lectrique du local Raccordement lectrique Un sch ma de c blage contenant les informations de connexion se trouve derri re le tableau de commande Si les codes locaux le permettent l a...

Page 26: ...rieur aliment s ensemble exigent une arriv e de 3 4 minimum Tuyauteries raccordements La s cheuse est fournie avec deux raccords d arriv e N P T de 1 2 l arri re Il est recommand de pr voir un robine...

Page 27: ...isation g n rale d alimentation en gaz si la pression en gaz naturel d passe 13 0 po CE 32 34 mbar Un piquage N P T de 1 8 minimum avec bouchon accessible pour raccorder un manom tre doit tre install...

Page 28: ...de mettre en marche la s cheuse contr ler les points suivants Lire toutes les tiquettes de DANGER AVERTISSEMENT MISE EN GARDE et CONSIGNE appos es la s cheuse Contr ler que la tension d alimentation...

Page 29: ...RQUE Les intervalles recommand s portent sur une utilisation moyenne en l occurrence 6 8 heures op rationnelles en fonctionnement par jour Tous les 6 mois inspecter le conduit d vacuation et liminer t...

Page 30: ...les trois ou quatre charges Si le filtre charpie est colmat le rendement de la s cheuse sera m diocre La trappe le tiroir du filtre charpie se trouve juste sous la porte de la s cheuse Ouvrir la trap...

Reviews: