38
OPERATIONS
•
If already in Diagnostic Status Report mode, press the
Fan Speed
key. The display will show the tem-
perature of the desired set point,
SP
; the temperature at
the wireless thermostat,
rL
; the indoor ambient tempera-
ture behind the filter,
IA
; the indoor coil temperature,
IC
;
the indoor discharge air temperature,
Id
; the outdoor coil
temperature,
OC
; the outdoor ambient temperature,
OA
;
and the spare probe temperature,
IH
. If any of the probes
are not populated, the display will show the corresponding
failure code.
Past Failure Log
•
If not in Diagnostic Status Report Mode, enter as instructed
above and press the Fan Speed
key twice.
•
If already in Diagnostic Status Report mode, press the
Fan Speed
key. While the display is showing oper-
ating temperatures, the last 10 failure codes active or past
can be requested by pressing the Fan Speed
key
again. The codes are displayed last entry first followed
subsequently by each preceding code.
Note that modes F1 and Fd are also displayed in the normal
control operation (see “Diagnostic Codes” chart).
To exit
Diagnostic Status Report mode,
press
the OFF
key.
DIAGNOSTIC CODES
STATUS
DISPLAY
ERROR
LIGHT
SUGGESTED ACTION
FP
Freeze
Protection
Engaged. The room temperature
measured by the wireless remote thermostat or indoor ambient
thermistor active sensor falls below 40°F.
Y
N
No Action required. This setting will disengage when the
room temperature rises above 43°F.
Fd
Front
Desk
switch is closed. All outputs are switched off.
Y
N
Open front desk switch to allow occupant unit operation.
Eo
Un-Configured Service Board -
All operation held awaiting configuration
Y
Y
Enter Configuration Menu and set "C3" to "C"
for coolers with electric heat or "H" for heat pumps.
EH
Emeregency Hydronic
Engaged. The EHH switch is closed.
Compressor is switched off.
Y
N
Open front emergency hydronic switch to allow occupant
unit operation.
LS
Load Shedding
Engaged. The LS switch is closed.
Compressor and Electric heat is switched off.
Y
N
Open load shedding switch
to allow occupant unit operation.
On
Control is configured to respond to a wired therm ostat
Y
N
No action if a wired thermostat is being used.
Otherwise, see Configuration Settings.
Indoor Ambient Thermistor reads outside the
range -20°F to 200°F
&
the wireless thermostat is not
communicating to the unit control or
Indoor Ambient Thermistor (IAT) without a wireless remote
thermostat reads outside the range -20°F to 200°F.
F2
Wireless Remote Thermostat failure
N
N
Replace Wireless Thermostat.
F3
Indoor Ambient Thermistor reads
outside the range -20°F to 200°F
Y
N
Replace black Indoor Ambient Thermistor.
F4
Indoor Coil Thermistor either above
or below operating tolerances.
N
Y
Replace Red Indoor Coil Threm istor .
F5
Wireless Thermostat failure.
N
Y
Attempt to rebind Wireless Thermostat
or Replace Wireless Thermostat.
F6
Indoor Discharge Thermistor either above
or below operating tolerances.
N
Y
Replace Yellow Indoor
Discharge Thermistor.
Fb
Low Remote Battery Warning.
N
Y
Replace Batteries in Wireless Devices.
H1
High Voltage Protection engaged.
Power supply voltage is to high.
Y
N
Check for incoming power at correct voltage.
br
Brown Out Protection engaged.
Power was lost or voltage is low.
N
N
Check for incoming power at correct voltage.
L6
Discharge Air Too Hot.
N
Y
Clean Filter or Remove Air Blockage.
LC
Outdoor Coil Thermistor temperature high.
N
Y
Clean Condenser Coils, Check Fan for
fault. Code will reset after cleaning.
C2
Indoor Air Recirculation. Large delta between thermostat and
return.
N
Y
Clean Filter or Remove Air Blockage or Close
Vent Door or Improve indoor to outdoor seal.
C5
Outdoor Coil temperature too high for outdoor ambient
temperature.
N
Y
Check for Blocked Outdoor Air or Clean Coil.
C3
Indoor Coil is freezing up.
N
Y
Clean filter, Check for fan and blower operation,
Check for Refrigerant loss
or Restricted capillary tube.
C4
Indoor Coil froze up.
N
Y
Clean filter, Check for fan and blower operation,
Check for Refrigerant loss
or Restricted capillary tube.
C6
Poor Unit Performance.
N
Y
Check for blower motor, compressor,
or electric heat operation.
RE
F
R
IG
E
R
AT
O
N
AL
E
R
T
S
CODE
MO
D
E
S
AI
R
F
L
O
W
AL
E
R
T
S
FA
IL
U
R
E
S
Replace black Indoor Ambient Thermistor or
Wireless Remote Thermostat.
Y
Y
F1