OPEN
STOP
CLOSE
MOTOR MOTION
Matrix 1
OPEN
STOP
CLOSE
MOTOR MOTION
Matrix 1
learn gate positions
8
1.
Push
OPEN
button to cycle gate to open position.
Operator cycles slowly while learning position.
2.
Then push
CLOSE
button to cycle gate to closed position.
Operator cycles slowly while learning position.
Set to MAX
MAX
GATE SPEED
MIN
MAX
Matrix 1
After gate positions have been learned, the gate will cycle at the speed set on matrix 1
“GATE SPEED”
setting.
Gate
Shut-Off
Switch
After the limit sensor activators and at least
ONE
entrapment sensor has been installed, put the gate in the
CLOSED
position:
IMPORTANT:
GATE SHUT-OFF
Switch
MUST
be
OFF
.
(see page 11 for more information about switch)
16
15 14 13
12
3
4
5
MAX
LED ON
Sensitivity
ERD
16
15 14 13
12
3
4
5
MAX
LED ON
Sensitivity
ERD
16
15 14 13
12
3
4
5
MAX
LED ON
Sensitivity
ERD
PhotoCell Edge
UL
Entrap
1
2
Limit SW
ON-LINE
MATRIX
JOG
JOG
LEFT RIGHT
Jog L
T
Jog R
T
GND
Edge 1
Edge 2
Photo
Cell
ERD
Motor
OverLoad
POWER
MC-200
Motor Controller
16
15 14 13
12
3
4
5
MAX
LED ON
Sensitivity
Edge
ERD
The
ERD Sensor
-
Electronic Reversing Device
(Type A)
MUST
be adjusted for the
OPEN and CLOSE gate cycles
.
When the gate encounters an obstruction during the
CLOSE
cycle, it will reverse to the open position and
PAUSE
the gate.
An input command (press remote button or exit loop) is needed
BEFORE
the gate will reset and close again.
When the gate encounters an obstruction during the
OPEN
cycle, it will reverse approximately 6 inches and
PAUSE
the gate.
An input command (press remote button or exit loop) is needed
BEFORE
the gate will reset and open again.
For the
ERD Sensitivity
to function correctly:
•
Limit sensors must be learned
BEFORE
adjusting the ERD Sensitivity.
A.
Turn knob until blue LED lights up.
Maximum sensitivity reached,
Position 1
- Too sensitive for most gates.
Position 13:
•
Typical gate setting.
B.
Turn knob
counter-clockwise
to
reduce gate sensitivity while testing ERD
until desired results is attained.
(LED remains OFF for all but position 1)
IMPORTANT:
When satisfied
with ERD adjustment, cycle
the gate 3 or 4 times to make
sure that the ERD sensor does
not
falsely trigger
during
normal gate operation.
Re-adjust if this happens.
CAUTION:
Position 16 results in gate exerting
MAXIMUM force
before reversing direction.
Adjusting ERD:
Typical Settings:
16 sensitivity setting positions.
NO mechanical hard stop for knob.
Position 16:
•
Heavy gate setting.
•
Long gate setting.
•
Cantilever gate setting.
•
Uphill gate setting.
•
High wind area gate setting.
OPEN
STOP
CLOSE
MOTOR MOTION
Matrix 1
Adjust ERD Reverse sensor
9
If alarm sounds while adjusting ERD,
press
STOP BUTTON
on Matrix 1 to
shut-off alarm.
16
15 14 13
12
3
4
5
MAX
LED ON
Sensitivity
ERD
8
UL 325 2016 Standard-MAX Quick Install Rev 8