i-32V5
Pompe di calore inverter aria/acqua con ventilatori assiali
40
Register
Format
Bit
R/W
Range
Name
Description
Note
954
BIT MASK
0
R
-
Alarms ⁴ ⁵
Module 2 probe 11 error
E713
1
Link inverter 1
E801
2
Link inverter 2
E802
3
Link inverter 3
E803
4
Hardware fault inverter 1
E851
5
Hardware fault inverter 2
E852
6
Hardware fault inverter 3
E853
7
Overcurrent inverter 1
E861
8
Overcurrent inverter 2
E862
9
Overcurrent inverter 3
E863
10
High temperature inverter 1
E871
11
High temperature inverter 2
E872
12
High temperature inverter 3
E873
13
Bad voltage inverter 1
E881
14
Bad voltage inverter 2
E882
15
Bad voltage inverter 3
E883
955
BIT MASK
0
R
-
Alarms ⁴ ⁵
Phase sequence inverter 1
E891
1
Phase sequence inverter 2
E892
2
Phase sequence inverter 3
E893
3
Model error inverter 1
E901
4
Model error inverter 2
E902
5
Model error inverter 3
E903
6
Overload error inverter 1
E911
7
Overload error inverter 2
E912
8
Overload error inverter 3
E913
9
Overcurrent PFC inverter 1
E921
10
Overcurrent PFC inverter 2
E922
11
Overcurrent PFC inverter 3
E923
12
Internal communication error inverter 1
E931
13
Internal communication error inverter 2
E932
14
Internal communication error inverter 3
E933
15
Fault PFC inverter 1
E941
956
BIT MASK
0
R
-
Alarms ⁴ ⁵
Fault PFC inverter 2
E942
1
Fault PFC inverter 3
E943
2
Probe error inverter 1
E951
3
Probe error inverter 2
E952
4
Probe error inverter 3
E953
5
Abnormal condition inverter 1
E961
6
Abnormal condition inverter 2
E962
7
Abnormal condition inverter 3
E963
8
Inverter 1 EEPROM error
E971
9
Inverter 2 EEPROM error
E972
10
Inverter 3 EEPROM error
E973
11
High discharge temperature of Cp3
E029
12
Anti-legionella performed correctly
E060
13
Anti-legionella failed or stopped
E061
¹⁾ if enabled
²⁾ the cycle is activated only if the DHW (4-5-6) status is terminated by the machine.
³⁾ if the read value is equal to 32766 the probe is not configured, if 32767 the probe is faulty.
⁴⁾ reset alarms, write the value 0 with the command 6 on any of the registers of the alarms area.
⁵⁾ the alarms of circuit 2 are mapped in the same way with an offset of 20000 (e.g. 20950).