37
i-32V5
Pompe di calore inverter aria/acqua con ventilatori assiali
Register
Format
Bit
R/W
Range
Name
Description
Note
1
INT
-
R
-
Firmaware informa
-
tion
Firmaware versione
2
INT
-
R
-
Firmware release
3
BYTE (H)
-
R
-
Firmware sub-release
BYTE (L)
-
R
-
Firmware creation day
4
BYTE (H)
-
R
-
Firmaware creation month
BYTE (L)
-
R
-
Firmware creation year
80 ÷ 97
ASCII
-
R
-
Serial number
Registration number
444
INT
-
R
0 ÷ 800
Water flow rate
1089
INT
-
R/W
1 ÷ 200
Serial address
Modbus serial ID
200
INT
-
R
-
Machine settings
(0) Stand by
Reading values of
the machine status
-
R
-
(1) Cooling
-
R
-
(2) Heating
-
R
-
(4)Only sanitary mode¹
-
R
-
(5) C Sanitary¹
-
R
-
(6) C Sanitary¹
7201
BIT MASK
0
R/W
-
Enablement of writing the machine
status remotely
Necessary for the
operation of the
reg. 7200.
7200
INT
-
W
-
(0) Stand by
The writing values
that are not allowed
at this address can
lead to unexpected
operations, so keep
only those values
that are allowed in
writing.
-
W
-
(1) Cooling
-
W
-
(2) Heating
-
W
-
(4) Only sanitary¹
-
W
-
(5) C Sanitary¹
-
W
-
(6) H Sanitary¹
7201
BIT MASK
1
R/W
-
Setpoint
Enablement of writing the machine
status remotely
Necessary for the
operation of the
reg. 7203/7208.
7203
°C/10
-
R/W
5.0 ÷ 23.0
Cooling
7204
°C/10
-
R/W
25.0 ÷ 55.0-
Heating
7205
°C/10
-
R/W
25.0 ÷ 55.0
Santary
7206
°C/10
-
R/W
5.0 ÷ 23.0
Second cooling
7207
°C/10
-
R/W
25.0 ÷ 55.0
Second heating
7208
°C/10
-
R/W
0.0 ÷ 80.0
DHW preparer
7201
BIT MASK
2
R/W
-
Second setpoint
Enabling the switching to the second
setpoint
Necessary for the
operation of bit 0 of
reg. 7202.
7202
BIT MASK
0
W
-
0=primary setpoints, 1=secondary
setpoint
Writing value
7217
BIT MASK
0
R
-
0=primary setpoints, 1=secondary
setpoint
Reading value
7201
BIT MASK
3
R/W
-
Room temperature
call
Enablement of remote room call writing
Necessary for the
operation of bit 1 of
reg. 7202.
7202
BIT MASK
1
R/W
-
Forced room temperature call remotely
7201
BIT MASK
4
R/W
-
Sanitary call
Enablement of remote sanitary call
writing
Necessary for the
operation of bit 1 of
reg. 7202.
7202
BIT MASK
2
R/W
-
Forced remote sanitary mode call
7201
BIT MASK
5
R/W
-
Anti-Legionella ²
Enablement of anti-legionella cycle
remotely
Necessary for the
operation of bit 3 of
reg. 7202.
7202
BIT MASK
3
R/W
-
Remote anti-legionella cycle request
activation
The bit must be 1
for the entire cycle
period.
7216
BIT MASK
5
R
-
Anti-legionella cycle in progress
6
Anti-legionella cycle failed or stopped
It remains at 1 until
the next cycle, or it
resets itself when
the board is turned
off.
7202
BIT MASK
5
R/W
-
Plant air-vent
Forced plant air-vent
Only if the machine
is in Stand By (0).
7202
BIT MASK
6
R/W
-
Santary disablig
Sanitary call prohibition (without exiting
from the actual mode + SAN function)
Active only if the
setting of bit 3 is
7201 (when the
room temp. call
is also managed
remotely).