23
i-32V5
Pompe di calore inverter aria/acqua con ventilatori assiali
TABLE 2. JOINT OPERATION, BRACKET 1
N°
INTERVENTION ORDER
(with setpoint not reached)
STATUS
OPERATION
r10
r15
r12
r16
r23
r24
4
1)
Heat pump
2) After r12 minutes,
boiler
3) After further r12 minutes,
plant inte-
gration heater
HEAT /
HEAT+SAN HEAT
1
0/1/2
Set the min-
utes
/
4/6
1/3
5
1)
Heat pump
2) After r16 minutes,
plant integration
heater
HEAT+SAN DHW
0/1
1
/
Set the
minutes
0/1/4
2/3
6
1)
Heat pump
2) After r16 minutes,
boiler
HEAT+SAN/ DHW
0/1
0/1/2
/
Set the
minutes
2/3/5/6 2/3
7
1)
Heat pump
2) After r16 minutes,
plant integration
heater
3) After further r16 minutes,
boiler
HEAT+SAN DHW
0/1
1
/
Set the
minutes
2/3
2/3
8
1)
Heat pump
2) After r16 minutes,
boiler
3) After further r16 minutes,
DHW inte-
gration heater
HEAT+SAN DHW
0/1
1
/
Set the
minutes
5/6
2/3
9
1)
Heat pump
2) After r12 minutes,
plant/DHW inte-
gration heater
HEAT /
HEAT+SAN HEAT/DHW
1
1
Set the min-
utes
Set the
minutesi
0
3
10 1)
Heat pump
2) After r12 minutes,
boiler
HEAT /
HEAT+SAN HEAT/DHW
0/1
0/1/2
Set the min-
utes
Set the
minutes
3/6
0
11
1)
Heat pump
2) After r12 minutes,
plant/DHW inte-
gration heater
3) After further r12 minutes,
boiler
HEAT /
HEAT+SAN HEAT/DHW
1
1
Set the min-
utes
Set the
minutes
3
3
12
1)
Heat pump
2) After r12 minutes,
boiler
3) After further r12 minutes,
plant/
DHW integration heater
HEAT /
HEAT+SAN HEAT/DHW
1
1
Set the min-
utes
Set the
minutes
6
3
TABLE 3. JOINT OPERATION, BRACKET 2
N°
ORDINE INTERVENTO
(with setpoint not reached)
STATUS
OPERATION
r10
r15
r12
r16
r23
r24
1
1)
Boiler
2) After r12 minutes,
heat pump
HEAT /
HEAT+SAN HEAT
0/1
0/1/2
Set the min-
utes
/
1/3/4/6 0/2
2
1)
Boiler
2) After r12 minutes,
plant integration
heater
3) After further r12 minutes,
heat pump
HEAT /
HEAT+SAN HEAT
1
0/1/2
Set the min-
utes
/
1/3
1/3
3
1)
Boiler
2) After r12 minutes,
heat pump
3) After further r12 minutes,
plant inte-
gration heater
HEAT /
HEAT+SAN HEAT
1
0/1/2
Set the min-
utes
/
4/6
1/3
4
1)
Plant integration heater
2) After r12 minutes,
heat pump
HEAT /
HEAT+SAN HEAT
1
0/1/2
Set the min-
utes
/
0/2/5
1/3
5
1)
Boiler
2) After r16 minutes,
heat pump
HEAT+SAN DHW
0/1
0/1/2
/
Set the min-
utes
2/3/5/6 0/1
6
1)
Boiler
2) After r16 minutes,
DHW integration
heater
3) After further r16 minutes,
heat pump
HEAT+SAN DHW
0/1
1
/
Set the min-
utes
2/3
2/3
7
1)
Boiler
2) After r16 minutes,
heat pump
3) After further r16 minutes,
DHW inte-
gration heater
HEAT+SAN DHW
0/1
1
/
Set the min-
utes
5/6
2/3
8
1)
DHW integration heater
2) After r16 minutes,
heat pump
HEAT+SAN DHW
0/1
1
/
Set the min-
utes
0/1/4
2/3
9
1)
Boiler
2) After r12 minutes,
heat pump
HEAT /
HEAT+SAN HEAT/DHW
1
1
Set the min-
utes
Set the min-
utes
3/6
0
10
1)
Boiler
2) After r12 minutes,
plant/DHW inte-
gration heater
3) After further r12 minutes,
heat pump
HEAT /
HEAT+SAN HEAT/DHW
1
1
Set the min-
utes
Set the min-
utes
3
3
11
1)
Boiler
2) After r12 minutes,
heat pump
3) After further r12 minutes,
plant/
DHW integration heater
HEAT /
HEAT+SAN HEAT / SANITARIO
1
1
Set the min-
utes
Set the min-
utes
6
3