9
i-32V5
Pompe di calore inverter aria/acqua con ventilatori assiali
5.
USER INTERFACE - CONTROLLER
Select the operating mode and manually reset any alarms.
Each time you press the key you have the following sequence:
OFF -> COOL -> HEAT -> OFF
If DHW is enabled, the sequence is the following:
OFF -> COOL -> COOL+SAN -> HEAT -> HEAT+SAN -> OFF
While setting the parameters, this key has the function of sending BACK by one level.
Grants access to the parameter setting menu and allows you to set the summer, winter and sanitary setpoint.
UP key. In the parameter setting mode, it allows you to move to a higher menu or to increase the parameter value when in “edit”
mode.
DOWN key. In the parameter setting mode, it allows you to move to a lower menu or to decrease the parameter value when in
“edit” mode.
5.1
MENU
The following are the main features for navigating the menus, especially describing functions which are not obvious. The main menu has the
following items:
MENU
LABEL
PASSWORD LEVEL
OTHER CONDITIONS
Setpoint
Set
User
Not accessible if connected to Hi-T2
Probes
tP
Installer
---
Alarms
Err
User
Only if active alarms
Digital input
Id
Installer
---
Parameters
Par
Installer
---
Password
PSS
User
---
Hours of operations
oHr
Installer
---
USB
USb
Installer
Only with pen drive with relevant update files
Versione Firmware
Fir
Installer
Version, Revision and Sub
Alarm log
Hist
Installer
Only if the log contains data
The PSS menu is accessed to enter the service password and to enable access with a higher user permission. When you have exited the menus,
the password must be entered once again to re-enter.
5.2
SETPOINT MENU
The various setpoints can be viewed and edited.
SETPOINT
DESCRIPTION
UNIT
DEFAULT
RANGE
Coo
First Summer setpoint
°C
7.0
5 ÷ Co2
Hea
First Winter setpoint
°C
45.0
25 ÷ 60
*San
Sanitary setpoint
°C
48.0
25 ÷ 60
Coo2
Second Summer setpoint
°C
18.0
Coo ÷ 25
Hea2
Second Winter setpoint
°C
35.0
25 ÷ Hea
San2
Second Sanitary setpoint
°C
35.0
25 ÷ Hea
**rCoo
Mixing valve Summer setpoint
°C
15.0
0.0 ÷ 80