control.
10.13
COMPRESSOR CRANKCASE HEATER
The crankcase heater is activated if the compressor has been off for at least 30 minutes and if the discharge temperature is below a certain
threshold of 20 °C (with hysteresis of 2.0°C). The crankcase heater is disabled when the compressor starts back up.
10.14 DOUBLE SET-POINT
This function introduces a second working set-point on the plant side, both in cooling and heating mode.
The user terminal board allows a consent to be connected to switch from the first to the second set-point and configured at digital input DI9 with
parameter
H53 = 26
. The valve, on the other hand, is connected in the terminal board to digital output DO7 and is configured via parameter
H85
.
Parameter
VALUE
Function
H53
26
Second set-point call
H85
25
3-way valve for radiant panels
H129
0
Function disabled (default)
1
Function configured but not active
2
Enabled only in cooling mode
3
Enabled only in heating mode
4
Enabled in cooling and heating mode
H138
0
DHW second setpoint function disabled (default)
1
Enabled the second DHW set point in cooling mode
2
Enabled the second DHW set point in heating mode
3
Enabled the second DHW set point in cooling and heating mode
10.15
MINIMUM HZ FUNCTIONALITY
Configuring parameter L02=1 and L03≠0 reduces the nominal operating Hz of the compressor.
Parameter
VALUE
Function
L02
0
Function not active
1
Enabling minimum Hz
L03
0
Function not active
1
Function active only in cooling mode
2
Function active only in heating mode
3
Function active only in sanitary mode
4
Function active in cooling and sanitary mode
5
Function active in heating and sanitary mode
6
Function active in cooling and heating mode
7
Function always active
With the function active, the output and power of the unit are limited, for additional information see the installer user manual.
Configuring a digital input DI9 with parameter H53=21, the function can be managed.
Parameter
VALUE
Function
H53
0 (default)
Function disabled
21
Open contact -> standard mode
Closed contact -> mode Hz min/max
10.16
MAXIMUM HZ FUNCTIONALITY
Activating the function increases the power of the unit, please contact us for information.
10.17
FLOWMETER
It is possible to connect a ratiometric flowmeter to CN7 terminals of the controller respecting the table below:
Connector
PIN 1
PIN 2
PIN3
CN7
GND
Voltage input
+5V
Terminal block
X-22.1
X-22.2
Connect it directly to pin 3 of CN7
of the controller
Enable the parameter H22=45 (configuration ST11).
I/O Resource - Parameter
Value
Function
H22
45
Water flow