HWA1-A
Air/water chillers with axial fans
26
H125 : PARITY, STOP BIT
0
NONE, 2 bit
1
ODD, 1 bit
2
EVEN, 1 bit
3
NONE, 1 bit
H126 : DEVICE ID
1 ÷ 200
Modbus comands:
READING
HOLDING
REGISTER
WRITING
6-16
Register
Format
Bit
R/W
Range
Name
Description
Note
1
INT
-
R
-
Data version
Firmware version
2
INT
-
R
-
Firmware release
3
BYTE (H)
-
R
-
Firmware sub-release
BYTE (L)
-
R
-
Firmware creation day
4
BYTE (H)
-
R
-
Firmware creation month
BYTE (L)
-
R
-
Firmware creation year
80 ÷ 97
ASCII
-
R
-
Serial number
Registration number
1089
INT
-
R/W
1 ÷ 200
Serial address
Modbus serial ID
200
INT
-
R
-
Machine setting
(0) Stand by
Reading values of the machine
status
-
R
-
(1) Cooling
-
R
-
(2) Heating
-
R
-
(4) Only sanitary mode ¹
-
R
-
(5) C Sanitary ¹
-
R
-
(6) H Sanitary ¹
7201
BIT MASK
0
R/W
-
Enablement of writing the machine
status remotely
Necessary for the operation of the
reg. 7200.
7200
INT
-
W
-
(0) Stand by
The writing values that are not
allowed at this address can lead to
unexpected operations, so keep
only those values that are allowed
in writing.
-
W
-
(1) Cooling
-
W
-
(2) Heating
-
W
-
(4) Only sanitary¹
-
W
-
(5) C Sanitary¹
-
W
-
(6) H Sanitary¹
7201
BIT MASK
1
R/W
-
Setpoint
Enablement of writing the setpoint
remotely
Necessary for the operation of the
reg. 7203/7208.
7203
°C/10
-
R/W
5.0 ÷ 23.0
Cooling
7204
°C/10
-
R/W
25.0 ÷ 55.0
Heating
7205
°C/10
-
R/W
25.0 ÷ 55.0
Sanitary
7206
°C/10
-
R/W
5.0 ÷ 23.0
Second cooling
7207
°C/10
-
R/W
25.0 ÷ 55.0
Second heating
7208
°C/10
-
R/W
0.0 ÷ 80.0
DHW preparer
7201
BIT MASK
2
R/W
-
Second setpoint
Enabling the switching to the second
setpoint
Necessary for the operation of bit
0 of reg. 7202.
7202
BIT MASK
0
W
-
0=primary setpoints, 1=secondary setpoint
Writing value
7217
BIT MASK
0
R
-
0=primary setpoints, 1=secondary setpoint
Reading value
7201
BIT MASK
3
R/W
-
Room
temperature call
Enablement of remote room call writing
Necessary for the operation of bit
1 of reg. 7202.
7202
BIT MASK
1
R/W
-
Forced room temperature call remotely
7201
BIT MASK
4
R/W
-
Sanitary call
Enablement of remote sanitary call
writing
Necessary for the operation of bit
2 of reg. 7202.
7202
BIT MASK
2
R/W
-
Forced remote sanitary mode call
7201
BIT MASK
5
R/W
-
Anti-Legionella ²
Enablement of anti-legionella cycle
remotely
Necessary for the operation of bit
3 of reg. 7202.
7202
BIT MASK
3
R/W
-
Remote anti-legionella cycle request
activation
The bit must be 1 for the entire
cycle period.
7216
BIT MASK
5
R
-
Anti-legionella cycle in progress
6
Anti-legionella cycle failed or stopped
It remains at 1 until the next cycle,
or it resets itself when the board is
turned off.
7202
BIT MASK
5
R/W
-
Plant air-vent
Forced pant air-vent
Only if the machine is in Stand By (0).