SET-POINT

’S

 CONFIGURATION PARAMETERS 

Parameter 

Description 

Unit 

Default 

Range 

Visibility 

Allowed configurations 

Notes 

Coo 

First setpoint in cooling 

°C 

7.0 

H03÷Co2 

USER 

 

 

Hea 

First setpoint in heating 

°C 

45.0 

He2÷H01 

USER 

 

 

San 

DHW (sanitary) setpoint 

°C 

48.0 

H02÷H01 

USER 

 

 

Co2 

Second setpoint in cooling 

°C 

18.0 

Coo÷H03 

USER 

 

 

He2 

second setpoint in heating 

°C 

35.0 

H02÷Hea  

USER 

 

 

18.2

 

CONFIGURATION PARAMETERS

 

Parameter 

Description 

Unit 

Default 

Range 

Visibility 

Allowed configurations 

Notes 

H01 

Maximum set point in heating 

°C 

63.0 

-50.0÷80.0 

INSTALLER 

 

 

H02 

Minimum set point in  heating 

°C 

25.0 

-50.0÷80.0 

INSTALLER 

 

 

H03 

Maximum set point in cooling 

°C 

25.0 

-50.0÷80.0 

INSTALLER 

 

 

H04 

Minimum set point in cooling 

°C 

5.0 

-50.0÷80.0 

INSTALLER 

 

 

*H85 

Configuration of digital input 

DO7 

0÷47 

INSTALLER 

0 = input not assigned 
21= Defrosting signalization 
24= Alarm signalization 
31=Plant season signalization 
47=Lock signalization 

D07, D07N terminals

 

H126 

Serial address 

1÷200 

INSTALLER 

In  case  of  several  units  installed  in  cascade 
configuration,  you  have  to  assign  different 
addresses for each controller.

  

 

(*) Only for HWA1-A version 

18.3

 

ALARM CONFIGURATION PARAMETERS 

Parameter 

Description 

Unit 

Default 

Range 

Visibility 

Allowed configurations

 

Note 

A08 

Antifreeze alarm activation setting 

°C 

-127÷127 

INSTALLER 

 

 

A09 

Antifreeze alarm hysteresis 

°C 

3.0 

0.0÷25.5 

INSTALLER 

 

 

A16 

Low pressure set in cooling operation 

Bar 

Based on the model 

4,0÷80,0 

INSTALLER 

 

 

A27 

Low pressure set in heating operation 

1.3 

0.0÷25.5 

INSTALLER 

 

 

18.4

 

SETTING PARAMETERS 

Parameter 

Description 

Unit 

Default 

Range 

Visibility 

Allowed configurations

 

Note 

b01 

Band in cooling mode 

°C 

2,0 

0÷10,0 

INSTALLER 

 

 

b02 

Band in heating mode 

°C 

2,0 

0÷10,0 

INSTALLER 

 

 

b03 

Differential in DHW mode 

°C 

4,0 

0÷10,0 

INSTALLER 

 

 

b05 

Hysteresis cut-off of the compressor in cooling and 

heating 

°C 

0.5 

0.0÷25.5 

INSTALLER 

Recommended values included 
between 1 and 1.5 
Other different values can ensure 
the proper operation of the unit 

 

b06 

DHW transitory output in heating 

sec 

45 

0÷255 

INSTALLER 

 

 

b08 

Enabling dynamic set 

0÷1 

INSTALLER 

 

 

b09 

Max Offset in cooling dynamic set  

°C 

3.0 

-50.0÷80.0 

INSTALLER 

 

 

b10 

Max Offset in heating dynamic set 

°C 

-3.0 

-50.0÷80.0 

INSTALLER 

 

 

b11 

Outdoor set temperature in cooling dynamic set 

°C 

25 

-127÷127 

INSTALLER 

 

 

b12 

Outdoor set temperature in heating dynamic set 

°C 

15 

-127÷127 

INSTALLER 

 

 

b13 

ΔT in co

oling 

°C 

-10.0 

-50.0÷80.0 

INSTALLER 

 

 

b14 

ΔT 

in heating 

°C 

10.0 

-50.0÷80.0 

INSTALLER 

 

 

b15 

Setpoint regulation band from 0-10V analog input 

°C 

5.0 

0.0÷10.0 

INSTALLER 

 

 

b16 

Scan time of compressors start-up 

sec 

60 

0÷255 

INSTALLER 

 

 

b20 

Enabling of 0-10V/ratiometric input 

0÷1 

INSTALLER 

0 = 0-10V input 
1 = ratiometric input 

 

b22 

Thermoregulation Hysteresis cut-off plant sensor 

°C 

1,5 

0.0÷25.5 

INSTALLER 

 

 

18.5

 

CONDENSATION PARAMETERS 

Parameter 

Description 

Unit 

Default 

Range 

Visibility 

Allowed configurations 

Notes 

F05 

Operation under compressor call 

0 ÷1 

INSTALLER 

 

 

F06 

Min fan speed 

30 

0 ÷100 

INSTALLER

 

 

 

F07 

Max silent fan speed in cooling mode 

Based on the model 

0 ÷100 

INSTALLER

 

 

 

F08 

Set of the pressure at the minimum speed of the fan in 

cooling mode 

Bar 

16.0 

-50.0÷80.0 

INSTALLER

 

 

 

F09 

Proportional band for modulation of the fan in cooling mode 

Bar 

0.0÷25.5 

INSTALLER

 

 

 

F10 

Delta cut-off fan adjustment 

Bar 

2.6 

0.0÷25.5 

INSTALLER

 

 

 

F11 

Hysteresis cut-off 

Bar 

1.3 

0.0÷25.5 

INSTALLER

 

 

 

F13 

Max fan speed in cooling mode 

Based on the model 

0 ÷100 

INSTALLER

 

 

 

F14 

Set of the pressure at the maximum fan speed in cooling 

Bar 

28 

-50.0÷80.0 

INSTALLER

 

 

 

F15 

Min fan speed in heating 

Based on the model 

0 ÷100 

INSTALLER

 

 

 

F16 

Max. silent fan speed in heating mode 

Based on the model 

0 ÷100 

INSTALLER

 

 

 

F17 

Set of the pressure at the minimum fan speed in heating 

Bar 

15.0 

-50.0÷80.0 

INSTALLER

 

 

 

F18 

Linear band for fan motor modulation in heating mode 

Bar 

7.0 

0.0÷25.5 

INSTALLER

 

 

 

F19 

Max. fan speed in heating mode 

Based on the model 

0 ÷100 

INSTALLER

 

 

 

F20 

Set of the pressure at the maximum fan speed in heating 

Bar 

6.8 

-50.0÷80.0 

INSTALLER

 

 

 

F25 

Time of forced free-cooling ventilation at 100% 

Minuti  Based on the model 

0.0 ÷ 25.5 

 

 

 

F26 

Outdoor temperature Offset for free-cooling activation 

°C 

Based on the model  -12.7 ÷ 12.7 

 

 

 

F27 

Free-cooling deactivation hysteresis 

°C 

Based on the model  -12.7 ÷ 12.7 

 

 

 

Summary of Contents for HWA1-A 0140

Page 1: ...WA1 H 0285 This manual has been created for informative purpose The company declines any responsibility for the results of any projecting or any installation based on the explanations and or on the te...

Page 2: ...ONTROL 9 7 1 SET POINT ADJUSTMENT FROM 0 10V INPUT 9 7 2 CALCULATION OF THE CORRECTION WITH 0 10V INPUT 10 7 3 CALCULATION OF THE CORRECTION WITH RATIOMETRIC INPUT 10 7 3 1 Settings for standard clima...

Page 3: ...20 17 4 SETTING PARAMETERS 21 17 5 CONDENSATION PARAMETERS 21 17 6 COMPRESSOR PARAMETERS CONFIGURATION 21 18 USER AND INSTALLER ALLOWED CONFIGURATION TABLES 21 18 1 SET POINT S CONFIGURATION PARAMETE...

Page 4: ...and competent in the existing rules in the country in which the appliance will be installed 3 GENERAL SAFETY GUIDELINES Before beginning to operate on the units every user has to be perfectly knowledg...

Page 5: ...er voltage To touch the equipment if you are not allowed If the lightning risk is high the unit must be protected the risk assessment must comply with the CEI EN 62305 2 regulation If there is a possi...

Page 6: ...e UP button In the setting mode this button allows you to move up to a higher menu or to increase the value of a parameter when you are in the edit mode DOWN button In the setting mode this button all...

Page 7: ...greater privilege Once you exit completely from the menus you lose the password privilege and need to re enter it 5 3 1 Setpoint menu You can display and change the various setpoints SETPOINT DESCRIP...

Page 8: ...ou can display the number of operating hours of the compressors and of the pumps Press the ESC button for 3 seconds to resets the actual number of operating hours Note that you can get access to the m...

Page 9: ...aged by the controller which calculates the compressor on and off events according to the setpoint based on heat within a differential If several compressors are configured the controller selects the...

Page 10: ...delay time between a compressor shutdown and shutdown of the next one 6 5 Deactivation of compressors for outdoor temperature If the outdoor temperature sensor is configured and is not in trouble so t...

Page 11: ...0 10V analogue input if enabled To enable the function you must set the H21 parameter to be 40 and change the values of the parameter b15 range 0 10 taking into account that if the input is at 0 volt...

Page 12: ...ulation of the circulator is linear type 8 1 Air purging of the system This function allows the air purging of the system to achieve this function the circulator will run at its maximum speed To enabl...

Page 13: ...draulic pump in anti freezing operation If the setting temperature is too low and the pump is off the pump will be activated automatically Pa P04 set antifreeze pump activation Pa P05 hysteresis pump...

Page 14: ...fan motor The condensation control is a function of the condensing pressure in chiller mode and the evaporation pressure in heat pump mode The fan speed can be independently controlled from the compre...

Page 15: ...nt the frost formation on the surface of the air air coil The frost formation on the evaporator which occurs more frequently at very low ambient temperatures in addition to greatly decreasing the ther...

Page 16: ...utput is active in COOLING operation The output is not active in heating operation The output is not active when the unit s OFF During the DHW production and defrosting cycle the output keeps the sett...

Page 17: ...ort Parameter Value Function H10 0 default Deactivated function 1 Active function in heating and cooling mode The remote on off function doesn t deactivate the domestic hot water production DHW 2 Acti...

Page 18: ...ction when the digital input is open Note If a temperature sensor is installed and configured this management will be ignored and the thermoregulation will be done on the basis of the detected tempera...

Page 19: ...below is reported an illustrating table regarding the operation of the system Mode of operation Active call of the heat pump Heating Temperature detected by the outlet sensor of the heat pump setpoin...

Page 20: ...ppropriately configured NC state connected on the terminals DI3E DI3E Thermostat contact normally open the secondary circulator will be activated Thermostat contact normally closed the secondary circu...

Page 21: ...SER AND INSTALLER The parameters can be activated and or edited by user or when using the installer password to get access in the CB Control menu which is located on the front panel of the unit DESCRI...

Page 22: ...6 COMPRESSOR PARAMETERS CONFIGURATION COMPRESSOR PARAMETERS CONFIGURATION Parameter Description Unit Default Range Visibility Allowed Configurations Notes n01 Output power from PC1 100 0 100 INSTALLER...

Page 23: ...output in heating sec 45 0 255 INSTALLER b08 Enabling dynamic set 0 0 1 INSTALLER b09 Max Offset in cooling dynamic set C 3 0 50 0 80 0 INSTALLER b10 Max Offset in heating dynamic set C 3 0 50 0 80 0...

Page 24: ...peration time of compressor with minimum frequency sec 60 0 255 INSTALLER 18 9 CONFIGURATION PARAMETERS OF GI Module PLANT MANAGEMENT Optional Parameter Description Unit Default Range Visibility Allow...

Page 25: ...peration If the discharge temperature drops below Pa C65 the alarm disappears and the compressors are again ready to operate 19 10E016 USAGE PUMP 1 THERMAL PROTECTION The alarm will be activated when...

Page 26: ...Antifreeze alarm Unit E006 Flow switch alarm Unit E009 High compressor s discharge temperature Unit E016 Usage pump 1 thermal overload protection Pump 1 E018 High temperature alarm in cooling operati...

Page 27: ...3 7208 7203 C 10 R W 5 0 23 0 Cooling 7204 C 10 R W 25 0 55 0 Heating 7205 C 10 R W 25 0 55 0 Sanitary 7206 C 10 R W 5 0 23 0 Second cooling 7207 C 10 R W 25 0 55 0 Second heating 7208 C 10 R W 0 0 80...

Page 28: ...C 10 R Compressors inhalation circuit 2 20433 C 10 R Compressor 1 discharge circuit 2 20434 C 10 R Compressor 2 discharge circuit 2 20435 C 10 R Compressor 3 discharge circuit 2 406 bar 100 R Pression...

Page 29: ...re fault inverter 1 E851 5 Hardware fault inverter 2 E852 6 Hardware fault inverter 3 E853 7 Overcurrent inverter 1 E861 8 Overcurrent inverter 2 E862 9 Overcurrent inverter 3 E863 10 High temperature...

Page 30: ...lla performed correctly E060 13 Anti legionella failed or stopped E061 if enabled the cycle is activated only if the DHW 4 5 6 status is terminated by the machine if the read value is equal to 32766 t...

Page 31: ......

Page 32: ...r Supervisor Notes Catalogo Catalogue Katalog Catalogue MCO14110G7720 06 Serie Series Serie Serie S rie HWA1 A H 0140 0285 AIR WATER CHILLERS AND HEAT PUMPS WITH AXIAL FANS Possible wasted electrical...

Reviews: