HWA1-A
Air/water chillers with axial fans
20
Value
Description
21
Signalization of defrosting period
•
The digital output is activated at the beginning of defrosting cycle, once the Pa d06 time period has terminated
•
The digital output is deactivated at the end of defrosting cycle, once the Pa d07 time period is terminated.
24
Signalization of heat pump alarms
31
Signalization of plant season
•
The output is active in cooling mode operation
•
The output is not active when the unit is in heating mode operation
•
The output is not active if the unit is OFF.
During the DHW production and defrosting cycle, the output keeps the settings of the provenance season.
47
The output is activated if one the below alarms is active and the following conditions must be fulfilled:
Alarm
Reste condition
E001
Manual
E002
Manual
E005
Manual
E006
Manual
E008
Manual
E018
Automatic
E041
Manual
E101
Automatic
E102
Automatic
Sensor error
Automatic
16
HANDBOOK FOR SOME CONFIGURATIONS OF INSTALLATION
For more information about some configurations, you can contact our office and ask for the handbook which collects a series of
some recommended highlighted drawings of plants regarding the installation configurations of our high efficiency heat pumps.
The "Handbook" shows the symbiotic potential with some of our products in the catalogue.
17
TABLES OF ALLOWED CONFIGURATIONS FOR THE USER AND INSTALLER
The parameters can be activated and/or edited by user or when using the installer password to get access in the CB Control menu
which is located on the front panel of the unit.
DESCRIPTION
GROUP IDENTIFICATION CODE
PARAMETER INDEX
VISIBILITY
Configuration
CnF
H-
USER/INSTALLER
Compressor
CP
C-
INSTALLER
Fan motor
FAn
F-
INSTALLER
Alarms
ALL
A-
INSTALLER
17.1
SETPOINT CONFIGURATION PARAMETERS
SETPOINT CONFIGURATION PARAMETERS
Parameter
Description
Unit
Default
Range
Visibility
Allowed configuration
Notes
Coo
First setpoint in cooling mode
°C
11 (mod. 255-272)
12 (mod. 142)
H03÷20.0
USER
17.2
CONFIGURATION PARAMETERS
Parameter
Description
Unit
Default
Range
Visibility
Allowed configurations
Notes
H03
Maximum set point in cooling
°C
23.0
-50.0÷80.0
INSTALLER
H04
Minimum set point in cooling
°C
9 (mod. 255-272)
10 (mod. 142)
-50.0÷80.0
INSTALLER
H47
DI3 configuration
/
2
0÷30
INSTALLER
0 = input not assigned
2 = Remote On / Off
Terminal: DI2/ DI2
H80
D02 under voltage digital
output
/
0
0÷47
INSTALLER
0 = output not assigned
24 = alarm notification
Under voltage output 230Vac,
50Hz, 5A resistive, 1A inductive;
Terminals of exchange contact
NC1, N1, NO1.
H126
Serial address
/
1
1÷120
INSTALLER
In case of installing 2 units or more in
cascade configuration, you have to assign
different addresses for each controller.
17.3
CONFIGURATION PARAMETERS OF THE ALARMS
CONFIGURATION PARAMETERS OF THE ALARMS
Parameter
Description
Unit
Default
Range
Visibility
Allowed configurations
Notes
A16
Low pressure set in cooling operation
Bar
according to
the model
4,0÷80,0
INSTALLER
Summary of Contents for HWA1-A 0140