HWA1-A
Air/water chillers with axial fans
27
7202
BIT MASK
6
R/W
-
Sanitary
disabling
Sanitary call prohibition (without exiting
from the actual mode + SAN function)
Active only if the setting of bit 3 is
7201 (when the room temp. call is
also managed remotely).
7202
BIT MASK
7
R/W
-
Defrosting
Forced defrosting
Only if the machine is in heating
(2-6).
7214
BIT MASK
13
R
-
Defrosting on call
14
Defrosting in progress
305
Hour
-
R
-
Operating hours
Compressor 1
307
Hour
-
R
-
Compressor 2
309
Hour
-
R
-
Compressor 3
313
Hour
-
R
-
Compressor 1 circuit 2
315
Hour
-
R
-
Compressor 2 circuit 2
317
Hour
-
R
-
Compressor 3 circuit 2
253
°C/10
-
R
-
Temperature
transducer
Evaporation
254
°C/10
-
R
-
Condensatzion
626
°C/10
-
R
-
Evaporatione circuit 2
627
°C/10
-
R
-
Condensation circuit 2
400
°C/10
-
R
-
Temperature ³
Water inlet
401
°C/10
-
R
-
Water outlet
405
°C/10
-
R
-
DHW
422
°C/10
-
R
-
Compressors inhalation
428
°C/10
-
R
-
Outdoor
433
°C/10
-
R
-
Exhaust of compressor 1
434
°C/10
-
R
-
Exhaust of compressor 2
435
°C/10
-
R
-
Exhaust of compressor 3
437
°C/10
-
R
-
Solar collector
438
°C/10
-
R
-
Solar accumulation
440
°C/10
-
R
-
Plant remote
443
°C/10
-
R
-
Mandata miscelatrice pannelli radianti
447
°C/10
-
R
-
DHW preparer recirculation
20422
°C/10
-
R
-
Compressors inhalation (circuit 2)
20433
°C/10
-
R
-
Compressor 1 discharge (circuit 2)
20434
°C/10
-
R
-
Compressor 2 discharge (circuit 2)
20435
°C/10
-
R
-
Compressor 3 discharge (circuit 2)
406
bar/100
-
R
-
Pressions ³
High pressure
414
bar/100
-
R
-
Low pressure
20406
bar/100
-
R
-
Circuit 2 high pressure
20414
bar/100
-
R
-
Circuit 2 low pressure
7000
%/10
-
R
-
Analog outputs
Condensation fan
7001
%/10
-
R
-
Circulating pump
627
%/10
-
R
-
Condensation fan of circuit 2
950
BIT MASK
0
R
-
Alarms
⁴ ⁵
High pressure
E001
1
Low pressure
E002
2
Compressor thermal protection
E003
3
Fan thermal protection
E004
4
Frost
E005
5
Lack of flow
E006
6
DHW preparer low temperature
E007
7
Lack of lubrication
E008
8
High discharge temperature of Cp1
E009
9
Solar collector at high temperature
E010
12
Compressor 2 thermal protection
E013
13
Fan 2 thermal protection
E014
15
Pump thermal protection
E016
951
BIT MASK
1
R
-
Alarms
⁴ ⁵
High temperature
E018
2
High discharge temperature of Cp2
E019
3
Inverted pressure transducers
E020
6
Compressor 3 thermal protection
E023
7
Fan 3 thermal protection
E024
9
Pump 2 thermal protection
E026
11
Temperature incongruenti
E041
12
Poor heat exchange DHW
E042
13
DHW accumulation tank in high
temperature
E050
14
I/O module 1 disconnected
E101
15
I/O module 2 disconnected
E102
952
BIT MASK
0
R
-
Alarms
⁴ ⁵
Probe 1 error
E611
1
Probe 2 error
E621
2
Probe 3 error
E631