HWA1-A
Air/water chillers with axial fans
6
5.2
Menu
’s
structure diagram
Level 0 (
U
) = It’s always visible
Level 1 (
M
) = it’s visible if you enter the maintainer or manufacturer password
Level 2 (
C
) = it’s visible if you enter the manufacturer password
Level 3 (
A
) = it’s visible only via Modbus
5.3
Menu
The main functions of the menus are listed below, especially when there are some unambiguous functions. The main menu
manages the following items
MENU
LABEL
LIVEL OF PASSWORD
OTHER CONDITIONS
Setpoint
Set
User
Not accessible if the Hi-T control panel is connected
Sonde
tP
Installer
---
Alarms
Err
User
Only in case of active alarms
Digital inputs
Id
Installer
---
Parameters
Par
Installer
---
Password
PSS
User
---
Number of operating hours
oHr
Installer
---
USB
USb
Installer
Only in the USB flash drive is present with its files
You need to access to the password menu for introducing the relative password and enable an access with a greater privilege.
Once you exit completely from the menus, you lose the password privilege and need to re-enter it.
5.3.1
Setpoint menu
You can display and change the various setpoints.
SETPOINT
DESCRIPTION
UNIT DEFAULT
RANGE
Coo
First setpoint in the summer
°C
7.0
H03
÷
Co2
Hea
First setpoint in the winter
°C
45.0
He2
÷
H01
*San
DHW setpoint
°C
48.0
H02
÷
H01
Co2
Second setpoint in the summer
°C
18.0
Coo
÷
H03
He2
Second setpoint in the winter
°C
35.0
H02
÷
Hea
5.3.2
Password menu
Enter the password for the desired access level. The controller will automatically activate the desired access level and then they
will appear on this level the functions which can be enabled from this level.
5.3.3
Sensors menu
The value of the various probes is displayed. The number of visible sensor depends on the presence of the I/O expansion modules.
Particular cases:
•
Err = Sensor is faulty
•
--- = Sensor not used (no function associated to such sensor)
By entering the maintainer password in the menu of analog inputs "tP", at the level 1 of the menu structure diagram of the on-
board control panel, you can read the values of the current probes:
Summary of Contents for HWA1-A 0140