Page | - 22 -
© Copyright Mastip Technology Limited. Information subject to alteration. V1.01 www.mastip.com
Temperature Controller METICOM CTI Series
1) Click the [Sensor Fault Solution] to enter its setting interface.
2) Set the Major ID and its Related ID. You can set up to 12 pairs.
3) Touch the [Enable] or [Disable] to activate or stop this function.
(
blue – unchecked,
green – checked)
4) Click [Quit] to close the interface.
5.2.11 Speed Related Setting
You can divide all zones into up to 4 groups (max.11 zones in each group, the zones not appointed will
be in the last group). The groups will start to work one by one in turn.
When the system starts, the first group will start to work. When each zone’s temperature arrives at
the target range (the tolerance can be set), the next group will start to work, until all the groups are
running.
Typically, the slower heating manifolds should be in the first group and the faster heating nozzles are
in the last group.
This function can be enabled or disabled according to requirements.
1) Click the [Speed Related Setting] to enter its setting interface.