Model: LC5296-XP-DC
Doc. Ref. no.:- m61D/om/401
Issue no.: 05
User’s Manual
Page 7 of 31
Isolation (Withstanding voltage)
Between primary terminals* and secondary terminals**:
At least 1500 V AC for 1 minute
Between primary terminals* and grounding terminal:
At least 1500 V AC for 1 minute
Between grounding terminal and secondary terminals**:
At least 1500 V AC for 1 minute
Between secondary terminals**:
At least 500 V AC for 1 minute
* Primary terminals indicate power terminals and relay output terminals.
** Secondary terminals indicate analog I/O signal and Communication O/P.
Insulation resistance:
20M
Ω or more at 500 V DC between power terminals and
grounding terminal.
2.6 Environmental Conditions
TEMPCO
For Input to PV Display < 100ppm.
For Display to Retransmission < 100ppm
Humidity
30% to 95% RH (Non-Condensing)
Instrument Warm-up Time
Approx. 15 minutes
Ambient temperature
0 to 55°C
Storage Temperature
0 to 80°C
2.7 Special Feature:
1 Relay mapping with respect to input no.
2 Retransmission output mapping with respect to input no.