6.1 RUN Time Indication/Function
Following parameters can view or change during run time.
In upper display, it shows Process value for input-1.
In lower display, it shows Process value for input-2.
6.2 Set Point Setting
Pressing SET key PV Display shows
C1.sp
(C1.SP) message. SV display shows
Control Set Point-1 Value
. Use Inc and Dec key to modify value. OR press MENU
key again to set value for
Control Set Point-2 Value.
6.3 CONFIGURATION MODE
Set Point Setting:
Parameter
(PV display)
Setting name a nd
descr iption
Def ault
va lue
Sho ws on ly
if
Symbol
Name
C1.SP
(
C1.sp
)
Control Set Point 1
Range Depending on PV
sensor type selected
100
-
C2.SP
(
C2.sp
)
Control Set Point 2
Range Depending on PV
sensor type selected
100
-
CONFIGUR ATION P AR AM E TERS
Parameter
(PV displ a y)
Setting Name & Description
Default
Value
Show if Only
Symbol
Name
IN 1
(
1n 1
)
Input-1 Type
Set PV Input -1 Type
rtd.1
/
rtd
/
0-5v
/
1-5v
/
0-10V
/
SERL
Value
Input Type Range
7
RTD.1
-199.9 to 850.0 °C
8
RTD
-200 to 850 °C
9
0-5 V /
0-20 mA*
-1999 to 1999
10
1-5 V / 4-
20 mA*
11
0-10 V
12
Serial
*
Use external 250ohms,0.1% for
current input
RTD.1
Zro.1
(
zro.1
)
Zero-1
Automatically change to the Input Lower
Range with changing of Input Type
(Refer Above Table)
Can be set to any value within the Input
Range & less the SPAN Value.
-199.9
(If RTD.1)