Model: LC5296-XP-DC
Doc. Ref. no.:- m61D/om/401
Issue no.: 05
User’s Manual
Page 17 of 31
SPN.1
(
spn.1
)
Span-1
Automatically change to the Input Higher
Range with changing of Input Type
(Refer Above Table)
Can be set to any value within the Input
Range & greater the ZERO Value.
850.0
(If RTD.1)
IN 2
(
1n 2
)
Input-2 Type
Set PV Input -2 Type
rtd.1
/
rtd
/
0-5V
/
1-5V
/
SERL
Value
Input Type Range
7
RTD.1
-199.9 to 850.0 °C
8
RTD
-200 to 850 °C
9
0-5 V /
0-20 mA*
-1999 to 1999
10
1-5 V / 4-
20 mA*
11
Serial
*
Use external 250ohms,0.1% for
current input
RTD.1
Zro.2
(
ZRo.2
)
Zero-2
Automatically change to the Input Lower
Range with changing of Input Type
(Refer Above Table)
Can be set to any value within the Input
Range & less the SPAN Value.
-199.9
(If RTD.1)
SPN.2
(
spn.2
)
Span-2
Automatically change to the Input Higher
Range with changing of Input Type
(Refer Above Table)
Can be set to any value within the Input
Range & greater the ZERO Value.
850.0
(If RTD.1)
FLTR
(
fltr
)
Filter
Filter for PV Input
no
/
yes
0 : NO
1 : YES
YES
T.SP1
(
t.sp1
)
Type of Set
Point
(Control
Set Point-1)
(Relay-1)
Set Type of Set Point 1
l-on
/
H-on
0 : L-ON (Lower ON)
1 : H-ON (Higher ON)
Refer ON-OFF Control on Page:22
L-ON
T.SP2
(
t.sp2
)
Type of Set
Point
(Control
Set Point-2)
(Relay-2)
Set Type of Set Point 2
l-on
/
H-on
0 : L-ON (Lower ON)
1 : H-ON (Higher ON)
Refer ON-OFF Control on Page:22
L-ON