- 16
MPL 206 A - MPL 226 A
GB
GB
2.4 T
ABLE
OF
TECHNICAL
CHARACTERISTICS
(1)
Limited - time running power (LTP) ISO 8528-1
It is the maximum power that, under the environment conditions established by the norm ISO 3046/1, the generator group it is able to disburse for a maximum
of 500 hours for year, of which a maximum of 300 hours among the interval of maintenance prescribed by the builder. It is accepted the operation to
this power conditions the duration of the group.
An overload of the 10% is admitted only for regulation.
(2)
Prime power (PRP) ISO 8528-1
It is the available maximum power for a variable power cycle that the generator group is able to disburse for a boundless number of hours for year among
the interval of maintenance prescribed by the builder and under the environment conditions established by the norm ISO 3046/1. The middle power during
a period of 24 hours, doesn't have to exceed 80% of the PRP.
An overload of the 10% is admitted only for regulation.
MAX POWER (LTP)
1
206
226
kVA
CONTINUOUS POWER (PRP)
2
180
205
kVA
POWER FACTOR (Cos
Φ
)
THREEPHASE VOLTAGE
V
Hz
GRADE OF PROTECTION
MAX TEMP. OF USE
°C
MIN TEMP. OF USE
°C
MAX ALTITUDE OF USE
m
COOLING AIR FLOW
m
3
/min
L
mm
DIMENSIONS
W
mm
H
mm
MASS
2950
2950
kg
TYPE
MANUFACTER
MODEL
BF 6M 1013 FC G2
BF 6M 1013 FC G3
DISPLACEMENT
cm
3
MAXIMUN POWER
243 / 178,7
268 / 197,1
CV - kW
n° OF CYLINDERS
RATED SPEED
rpm
SPEED CONTROL
INDUCTION SYSTEM
FUEL
INJECTION SYSTEM
FUEL FEEDING PUMPS
FUEL TANK CAPACITY
L
AUTONOMY AT 3/4 LOAD
12,5
11,5
h
COOLING
LUBRIFICATION SYSTEM
OIL SUMP CAPACITY
L
COMBUSTION AIR VOLUME
13,5
14,3
m
3
/min
EXHAUST GAS MASS FLOW
14,3
16,3
m
3
/min
ELECTRIC PLANT
V
STARTING
STARTING MOTOR
V - kW
STARTING BATTERY
V - Ah
BATTERY CHARGER
V - A
STOPPING SYSTEM
TYPE
ISOLATION CLASS
VOLTAGE REGULATOR
VOLTAGE STABILITY
FREQUENCY STABILITY
COOLING
POWER FACTOR (Cos
Φ
)
CONTINUOUS POWER A.C.
GENERAL FEATURES
ALTERNATOR
ENGINE
RATED FREQUENCY
-15
1000
90
0,8
400
50
±
5%
MODEL
SINGLEPHASE 230V
MPL 206 A
MPL 226 A
SYNCHRONOUS, 4 POLES, SELF-REGULATED
H
ELECTRONIC
±
2%
40
IP 23
3613
1300
1904
4 STROKE
DEUTZ
7146
6
1500
MECHANICAL
DIESEL
DIRECT
TURBO/INTERCOOLER
MECHANICAL
400
WATER
FORCED
17
28 - 35
STOP SOLENOID VALVE
24
ELECTRIC
24 - 3,1
2 x (12 - 140)
AIR
1