background image

IOM  -  

RXTS Series

13

Important Safety 

Instructions

WARNINGS (for using R290/R32 refrigerant only)

j) When the cylinders have been filled correctly and the process completed, make sure that 

the cylinders and the equipment are removed from site promptly and all isolation valves on 

the equipment are closed off.

k) Recovered refrigerant shall not be charged into another refrigeration system unless it has 

been cleaned and checked.

15. Labeling

Equipment shall be labelled stating that it has been de-commissioned and emptied of 

refrigerant. The label shall be dated and signed. Ensure that there are labels on the 

equipment stating the equipment contains flammable refrigerant.

16. Recovery

When removing refrigerant from a system, either for servicing or decommissioning, it is 

recommended good practice that all refrigerants are removed safely.

When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery 

cylinders are employed. Ensure that the correct number of cylinders for holding the total 

system charge is available. All cylinders to be used are designated for the recovered 

refrigerant and labelled for that refrigerant (i.e. special cylinders for the recovery of 

refrigerant). Cylinders shall be complete with pressure relief valve and associated shut-off 

valves in good working order. Empty recovery cylinders are evacuated and, if possible, 

cooled before recovery occurs.

The recovery equipment shall be in good working order with a set of instructions concerning 

the equipment that is at hand and shall be suitable for the recovery of flammable refrigerants.

In addition, a set of calibrated weighing scales shall be available and in good working order. 

Hoses shall be complete with leak-free disconnect couplings and in good condition. Before 

using the recovery machine, check that it is in satisfactory working order, has been properly 

maintained and that any associated electrical components are sealed to prevent ignition in 

the event of a refrigerant release. Consult manufacturer if in doubt.

The recovered refrigerant shall be returned to the refrigerant supplier in the correct recovery 

cylinder, and the relevant Waste Transfer Note arranged. Do not mix refrigerants in recovery 

units and especially not in cylinders. If compressors or compressor oils are to be removed, 

ensure that they have been evacuated to an acceptable level to make certain that flammable 

refrigerant does not remain within the lubricant. The evacuation process shall be carried out 

prior to returning the compressor to the suppliers. Only electric heating to the compressor 

body shall be employed to accelerate this process. When oil is drained from a system, it shall 

be carried out safely. 

 Page 13 

Summary of Contents for Comfort-Aire RXTS Series

Page 1: ...IOM RXTS Series 1 www comfort aire com Installation and Operation Manual RXTS Series U Rack Window Type Room Air Conditioner RXTS 81A RXTS 101A RXTS 121A...

Page 2: ...RXTS Series 2 Table of Contents Important Safety Instructions 03 Installation Instructions 14 Normal Sounds Sound Performance 28 Air Conditioner Features 29 Care and Cleaning 33 Troubleshooting Tips...

Page 3: ...e possibility of injury or damage to property Indicates information considered important but not hazard related WARNING DANGER Plug in power plug properly Do not modify power cord length Always ensure...

Page 4: ...the power cord near flammable gas or combustibles such as gasoline benzene thinner etc Keep firearms away WARNING When the air filter is to be removed do not touch the metal parts of the unit It may...

Page 5: ...not drink water drained from air conditioner Do not place obstacles around air inlets or inside of air outlet Use caution when unpacking and installing Sharp edges could cause injury CAUTION If water...

Page 6: ...s Your air conditioner must be used in a properly grounded wall receptacle If the wall receptacle you intend to use is not adequately grounded or protected by a time delay fuse or circuit breaker have...

Page 7: ...pecified for operation Any person who is involved with working on or breaking into a refrigerant circuit should hold a current valid certificate from an industry accredited assessment authority which...

Page 8: ...gnition of the flammable refrigerant used Please follow the instructions carefully to store or maintain the air conditioner to prevent mechanical damage from occurring Flammable refrigerant R32 is use...

Page 9: ...Work in confined spaces shall be avoided The area around the workspace shall be sectioned off Ensure that the conditions within the area have been made safe by control of flammable material 4 Checkin...

Page 10: ...g corroded or are suitably protected against being so corroded 9 Checks to electrical devices Repair and maintenance to electrical components shall include initial safety checks and component inspecti...

Page 11: ...shall not be used 11 Leak detection methods The following leak detection methods are deemed acceptable for systems containing flammable refrigerants Electronic leak detectors shall be used to detect...

Page 12: ...e taken not to overfill the refrigeration system Prior to recharging the system it shall be pressure tested with OFN The system shall be leak tested on completion of charging but prior to commissionin...

Page 13: ...ief valve and associated shut off valves in good working order Empty recovery cylinders are evacuated and if possible cooled before recovery occurs The recovery equipment shall be in good working orde...

Page 14: ...IOM RXTS Series 14 Installation Instructions NOTICE The unit you purchased may look like one of the followings Page 14 Installation Instructions Model A Model B...

Page 15: ...IOM RXTS Series 15 Page 15 Installation Instructions NOTICE All the illustrations in this manual are for explanation purpose only The actual installation may vary Model C Model D...

Page 16: ...se IMPORTANT Observe all governing codes and ordianaces Note to Installer Be sure to leave these instructions with the Consumer Note to Consumer Keep these instructions for future reference Skill leve...

Page 17: ...pe B Screw 2 2 Window Sash Lock Window Sash Foam Window Sealing Foam Bracket Sealing Foam Additional Side Arm Foam 1 Type A Screw 2 2 1 1 1 1 Angled Support Arms Horizontal Bracket Spring Push Pin Mai...

Page 18: ...in adjust the Left Extension Arm out and then install the Right Extension Arm Measure the width of the inner windowsill on your window Making sure that the center of the bracket will line up with the...

Page 19: ...wsill by drilling 1 8 pilot holes and installing the 1 2 and 1 Type A screws as shown in Fig 7 B Move the Angled Support Arms toward the exterior wall until the feet touch the wall Place the level on...

Page 20: ...level again and ensure the bracket feels secure After making any necessary adjustments insert the cotter pins into the Main Support Pins Cotter Pin E If necessary cover the holes on the front of the b...

Page 21: ...n top of the support bracket Ensure the grooves on the bottom of the air conditioner align with the Main Supports Using a level check for proper tilt towards the outside WARNING Do not leave the unit...

Page 22: ...screws as shown Use the 1 2 Type B screw Use the 1 4 Type B screw Fig 16 A Measure the distance between the Side Arm Hinge and the closest part of the window frame in line with the Side Arm Add 1 4 t...

Page 23: ...conditioner Air Conditioner Side Vinyl Type Windows with Lipped Sill Window Sealing Foam Fig 18 Additional Side Arm Foam Wooden Type Windows with Flat Sill Window Sealing Foam Fig 19 Fig 20 C Insert S...

Page 24: ...iew Extend into Window Track The factory installed 1 2 screw must be re used to secure the Anti Tip Bracket Failing to use this screw could damage the air conditioner Top of Unit D The Anti Tip Bracke...

Page 25: ...Extend the Integrated Window Locks located in the U channel until they contact the window For additional security you can install the optional Sash Lock as shown Fig 25 Fig 26 FOAM SEAL Fig 24 G To s...

Page 26: ...drain holes or slots are not caulked or painted shut Accum ulated rain water or condensation must be allowed to drain out You must secure the support bracket to the added wood piece using the provided...

Page 27: ...its bottom portion 75 150cm above the floor level 6 The power cord must be connected to an independent circuit The yellow green wire must be grounded Installations of the unit into the wall OPTION A...

Page 28: ...In front of the unit you may hear the sound of rushing air being moved by the fan High Pitched Chatter Vibration Unit may vibrate and Trickling Sound Gurgle Hiss noises may be heard NOTICE All the il...

Page 29: ...w see Air Directional Louvers 6 Once the room has cooled adjust the thermostat to the setting you find most comfortable 7 Make sure the air flow inside and outside is not obstructed by anything Coolin...

Page 30: ...he timer settings Press or hold the UP or DOWN button to change the Auto time by 0 5 hour increments up to 10 hours then at 1 hour increments up to 24 hours The control will count down the time remain...

Page 31: ...e fan speed cannot be adjusted it starts automatically at a speed according to the room temperature 2 To operate on COOL mode Choose Cool Mode to set the cooling function Use the Up and Down buttons t...

Page 32: ...n automatic 3 minutes time delayed start if the unit is turned off and on quickly This prevents overheating of the compressor and possible circuit breaker tripping The fan will continue to run during...

Page 33: ...r from the filter Be sure the filter is thoroughly dry before replacing Instead of washing you may vacuum the filter clean Cabinet Cleaning Be sure to unplug the air conditioner to prevent shock or fi...

Page 34: ...filter Refer to Care and Cleaning section To defrost set to FAN ONLY mode Thermostat set too cold for night time cooling To defrost the coil set to FAN ONLY mode Then set temperature to a higher sett...

Page 35: ...ty of moisture from humid room This is normal during excessively humid days Remote Sensing Deactivating Prematurely some models Remote control not located within range Place remote control within 20 f...

Page 36: ...__________________________ _____________________________________________________________________________________ _____________________________________________________________________________________ _...

Page 37: ...__________________________ _____________________________________________________________________________________ _____________________________________________________________________________________ _...

Page 38: ...__________________________ _____________________________________________________________________________________ _____________________________________________________________________________________ _...

Page 39: ...emedy under the Limited Warranty is replacement of the defective unit Labor to diagnose and replace the defective unit is not covered by this Limited Express Warranty If for any reason the replacement...

Page 40: ...HQVLRQDO GDWD RQ WKH DFWXDO SURGXFW SULRU WR EHJLQQLQJ DQ LQVWDOODWLRQ SUHSDUDWLRQV QFHQWLYH DQG UHEDWH SURJUDPV KDYH SUHFLVH UHTXLUHPHQWV DV WR SURGXFW SHUIRUPDQFH DQG FHUWLILFDWLRQ OO SURGXFWV PHHW...

Reviews: