WARNINGS (for using R290/R32 refrigerant only)

7) Ventilated area

   Ensure that the area is in the open or that it is adequately ventilated before breaking into the 

   system or conducting any hot work. A degree of ventilation shall continue during the period 

   that the work is carried out. The ventilation should safely disperse any released refrigerant 

   and preferably expel it externally into the atmosphere.

8) Checks to the refrigeration equipment

   Where electrical components are being changed, they shall be fit for the purpose and to the 

   correct specification. At all times the manufacturer's maintenance and service guidelines 

   shall be followed. If in doubt consult the manufacturer's technical department for assistance.

   The following checks shall be applied to installations using flammable refrigerants:

   The charge size is in accordance with the room size within which the refrigerant containing 

   parts are installed;

   The ventilation machinery and outlets are operating adequately and are not obstructed;

   If an indirect refrigerating circuit is being used, the secondary circuit shall be checked for 

   the presence of refrigerant;

   Marking to the equipment continues to be visible and legible. Markings and signs that are 

   illegible shall be corrected;

   Refrigeration pipe or components are installed in a position where they are unlikely to be 

   exposed to any substance which may corrode refrigerant containing components, unless 

   the components are constructed of materials which are inherently resistant to being 

   corroded or are suitably protected against being so corroded.

9) Checks to electrical devices

   Repair and maintenance to electrical components shall include initial safety checks and 

   component inspection procedures. If a fault exists that could compromise safety, then no 

   electrical supply shall be connected to the circuit until it is satisfactorily dealt with. If the 

   fault cannot be corrected immediately but it is necessary to continue operation, an adequate 

   temporary solution shall be used. This shall be reported to the owner of the equipment so all 

   parties are advised.

   Initial safety checks shall include:

   That capacitors are discharged: this shall be done in a safe manner to avoid possibility of 

   sparking;

   That there no live electrical components and wiring are exposed while charging, recovering 

   or purging the system;

   That there is continuity of earth bonding.

7. Repairs to sealed components

1) During repairs to sealed components, all electrical supplies shall be disconnected from the 

   equipment being worked upon prior to any removal of sealed covers, etc. If it isabsolutely 

   necessary to have an electrical supply to equipment during servicing, then a permanently 

   operating form of leak detection shall be located at the most critical point to warn of a 

   potentially hazardous situation.

2) Particular attention shall be paid to the following to ensure that by working on electrical 

   components, the casing is not altered in such a way that the level of protection is affected.

   This shall include damage to cables, excessive number of connections, terminals not made 

   to original specification, damage to seals, incorrect fitting of glands, etc.

   Ensure that apparatus is mounted securely.

Important Safety 

Instructions

 Page 10

Summary of Contents for Comfort-Aire RXTS Series

Page 1: ...IOM RXTS Series 1 www comfort aire com Installation and Operation Manual RXTS Series U Rack Window Type Room Air Conditioner RXTS 81A RXTS 101A RXTS 121A...

Page 2: ...RXTS Series 2 Table of Contents Important Safety Instructions 03 Installation Instructions 14 Normal Sounds Sound Performance 28 Air Conditioner Features 29 Care and Cleaning 33 Troubleshooting Tips...

Page 3: ...e possibility of injury or damage to property Indicates information considered important but not hazard related WARNING DANGER Plug in power plug properly Do not modify power cord length Always ensure...

Page 4: ...the power cord near flammable gas or combustibles such as gasoline benzene thinner etc Keep firearms away WARNING When the air filter is to be removed do not touch the metal parts of the unit It may...

Page 5: ...not drink water drained from air conditioner Do not place obstacles around air inlets or inside of air outlet Use caution when unpacking and installing Sharp edges could cause injury CAUTION If water...

Page 6: ...s Your air conditioner must be used in a properly grounded wall receptacle If the wall receptacle you intend to use is not adequately grounded or protected by a time delay fuse or circuit breaker have...

Page 7: ...pecified for operation Any person who is involved with working on or breaking into a refrigerant circuit should hold a current valid certificate from an industry accredited assessment authority which...

Page 8: ...gnition of the flammable refrigerant used Please follow the instructions carefully to store or maintain the air conditioner to prevent mechanical damage from occurring Flammable refrigerant R32 is use...

Page 9: ...Work in confined spaces shall be avoided The area around the workspace shall be sectioned off Ensure that the conditions within the area have been made safe by control of flammable material 4 Checkin...

Page 10: ...g corroded or are suitably protected against being so corroded 9 Checks to electrical devices Repair and maintenance to electrical components shall include initial safety checks and component inspecti...

Page 11: ...shall not be used 11 Leak detection methods The following leak detection methods are deemed acceptable for systems containing flammable refrigerants Electronic leak detectors shall be used to detect...

Page 12: ...e taken not to overfill the refrigeration system Prior to recharging the system it shall be pressure tested with OFN The system shall be leak tested on completion of charging but prior to commissionin...

Page 13: ...ief valve and associated shut off valves in good working order Empty recovery cylinders are evacuated and if possible cooled before recovery occurs The recovery equipment shall be in good working orde...

Page 14: ...IOM RXTS Series 14 Installation Instructions NOTICE The unit you purchased may look like one of the followings Page 14 Installation Instructions Model A Model B...

Page 15: ...IOM RXTS Series 15 Page 15 Installation Instructions NOTICE All the illustrations in this manual are for explanation purpose only The actual installation may vary Model C Model D...

Page 16: ...se IMPORTANT Observe all governing codes and ordianaces Note to Installer Be sure to leave these instructions with the Consumer Note to Consumer Keep these instructions for future reference Skill leve...

Page 17: ...pe B Screw 2 2 Window Sash Lock Window Sash Foam Window Sealing Foam Bracket Sealing Foam Additional Side Arm Foam 1 Type A Screw 2 2 1 1 1 1 Angled Support Arms Horizontal Bracket Spring Push Pin Mai...

Page 18: ...in adjust the Left Extension Arm out and then install the Right Extension Arm Measure the width of the inner windowsill on your window Making sure that the center of the bracket will line up with the...

Page 19: ...wsill by drilling 1 8 pilot holes and installing the 1 2 and 1 Type A screws as shown in Fig 7 B Move the Angled Support Arms toward the exterior wall until the feet touch the wall Place the level on...

Page 20: ...level again and ensure the bracket feels secure After making any necessary adjustments insert the cotter pins into the Main Support Pins Cotter Pin E If necessary cover the holes on the front of the b...

Page 21: ...n top of the support bracket Ensure the grooves on the bottom of the air conditioner align with the Main Supports Using a level check for proper tilt towards the outside WARNING Do not leave the unit...

Page 22: ...screws as shown Use the 1 2 Type B screw Use the 1 4 Type B screw Fig 16 A Measure the distance between the Side Arm Hinge and the closest part of the window frame in line with the Side Arm Add 1 4 t...

Page 23: ...conditioner Air Conditioner Side Vinyl Type Windows with Lipped Sill Window Sealing Foam Fig 18 Additional Side Arm Foam Wooden Type Windows with Flat Sill Window Sealing Foam Fig 19 Fig 20 C Insert S...

Page 24: ...iew Extend into Window Track The factory installed 1 2 screw must be re used to secure the Anti Tip Bracket Failing to use this screw could damage the air conditioner Top of Unit D The Anti Tip Bracke...

Page 25: ...Extend the Integrated Window Locks located in the U channel until they contact the window For additional security you can install the optional Sash Lock as shown Fig 25 Fig 26 FOAM SEAL Fig 24 G To s...

Page 26: ...drain holes or slots are not caulked or painted shut Accum ulated rain water or condensation must be allowed to drain out You must secure the support bracket to the added wood piece using the provided...

Page 27: ...its bottom portion 75 150cm above the floor level 6 The power cord must be connected to an independent circuit The yellow green wire must be grounded Installations of the unit into the wall OPTION A...

Page 28: ...In front of the unit you may hear the sound of rushing air being moved by the fan High Pitched Chatter Vibration Unit may vibrate and Trickling Sound Gurgle Hiss noises may be heard NOTICE All the il...

Page 29: ...w see Air Directional Louvers 6 Once the room has cooled adjust the thermostat to the setting you find most comfortable 7 Make sure the air flow inside and outside is not obstructed by anything Coolin...

Page 30: ...he timer settings Press or hold the UP or DOWN button to change the Auto time by 0 5 hour increments up to 10 hours then at 1 hour increments up to 24 hours The control will count down the time remain...

Page 31: ...e fan speed cannot be adjusted it starts automatically at a speed according to the room temperature 2 To operate on COOL mode Choose Cool Mode to set the cooling function Use the Up and Down buttons t...

Page 32: ...n automatic 3 minutes time delayed start if the unit is turned off and on quickly This prevents overheating of the compressor and possible circuit breaker tripping The fan will continue to run during...

Page 33: ...r from the filter Be sure the filter is thoroughly dry before replacing Instead of washing you may vacuum the filter clean Cabinet Cleaning Be sure to unplug the air conditioner to prevent shock or fi...

Page 34: ...filter Refer to Care and Cleaning section To defrost set to FAN ONLY mode Thermostat set too cold for night time cooling To defrost the coil set to FAN ONLY mode Then set temperature to a higher sett...

Page 35: ...ty of moisture from humid room This is normal during excessively humid days Remote Sensing Deactivating Prematurely some models Remote control not located within range Place remote control within 20 f...

Page 36: ...__________________________ _____________________________________________________________________________________ _____________________________________________________________________________________ _...

Page 37: ...__________________________ _____________________________________________________________________________________ _____________________________________________________________________________________ _...

Page 38: ...__________________________ _____________________________________________________________________________________ _____________________________________________________________________________________ _...

Page 39: ...emedy under the Limited Warranty is replacement of the defective unit Labor to diagnose and replace the defective unit is not covered by this Limited Express Warranty If for any reason the replacement...

Page 40: ...HQVLRQDO GDWD RQ WKH DFWXDO SURGXFW SULRU WR EHJLQQLQJ DQ LQVWDOODWLRQ SUHSDUDWLRQV QFHQWLYH DQG UHEDWH SURJUDPV KDYH SUHFLVH UHTXLUHPHQWV DV WR SURGXFW SHUIRUPDQFH DQG FHUWLILFDWLRQ OO SURGXFWV PHHW...

Reviews: