Diagnostic Programming Mode
NOTE: Depending on current option settings, some displays cannot be viewed.
Overview Diagnostic Mode
The current Diagnostic Programming Mode screen will display until either the Extra Cycle button is pressed
through for each screen, or the Diagnostic button is pressed. In the event of regeneration occurring while in the
Diagnostic Programming Mode, the regeneration step and time remaining will be displayed. When regeneration
completes, the display will return to the normal time of day display screen.
Entering and Exiting Diagnostic Mode
Press and release the “D” button to enter the Diagnostic Programming Mode. Pressing the Extra Cycle button will
move to the next diagnostic screen. Press the Extra Cycle button once per display until all are viewed. Pressing
the Diagnostic button while in Diagnostic Mode will cause the unit to leave the Diagnostic Mode and return to the
normal time of day display screen.
Current Flow Rate
This program step displays the calculated flow rate for the timer. The below flow rates are the maximum flow
rate the timer will read for each meter.
.75” Paddle:
15 gpm (0.06 m3/m)
.75” Turbine:
15 gpm (0.06 m3/m)
1” Paddle:
40 gpm (0.15 m3/m)
1” Turbine:
90 gpm (0.34 m3/m)
1.5” Paddle:
180 gpm (0.68 m3/m)
1.5” Turbine:
90 gpm (0.34 m3/m)
2” Paddle:
350 gpm (1.32 m3/m)
3” Paddle:
500 gpm (1.89 m3/m)
— Press the Extra Cycle button.
Peak Flow Rate
This program step displays the peak flow rate since the last regeneration.
— Press the Extra Cycle button.
Totalizer
This program step displays the total volume of treated water that passes through the meter.
— Reset to zero by holding the Up and Down buttons for five seconds while in the totalizer screen.
— Press the Extra Cycle button.
Hours Between Last Two Regenerations
This program step displays the time between the last two regenerations saved.
— Press the Extra Cycle button.
Hours Since Last Regeneration
This program step displays the hours since the last regeneration.
— Press the Extra Cycle button.
Volume Remaining
This program step displays the volume remaining. The timer will regenerate if the volume remaining is set to
zero. The maximum ranges are the same as the maximum volume calculated on the main screen.
— Press the Extra Cycle button.
Reserve Capacity
This program step displays the reserve capacity, ensuring soft water is available at all times.
— Press the Extra Cycle button.
Previous Day’s Water Usage
This program step displays the previous day’s water usage.
— Press the Extra Cycle button.
Software Version
This program step displays the timer’s software program version number.
— Press the Extra Cycle button to exit.
NOTE: Diagnostic Programming Mode will stop if the system goes into a regeneration.
1.
2.
3.
4.
5.
6.
7.
8.
9.
Page 3
6
MAT
D
9500 XT MANUAL
Summary of Contents for MATD 9500 XT
Page 4: ......
Page 7: ...9500 Control Dimensions Page 4 MATD 9500 XT MANUAL ...
Page 11: ...Page 8 ...
Page 19: ...Page 16 WATER CONDITIONER FLOW DIAGRAMS MATD 9500 XT MANUAL ...
Page 20: ...Page 17 WATER CONDITIONER FLOW DIAGRAMS MATD 9500 XT MANUAL ...
Page 21: ...Page 18 WATER CONDITIONER FLOW DIAGRAMS MATD 9500 XT MANUAL ...
Page 40: ...9500 Power Head Assy 61501 3200XT 9_REVA Page 37 MATD 9500 XT MANUAL ...
Page 42: ...9500XT Wiring 42140_2750XT_2850XT_REVA 0_2750XT_2850XT_REVA Page 39 MATD 9500 XT MANUAL ...
Page 43: ...Page 40 9100 9500 MATD 9500 XT MANUAL ...
Page 44: ...Page 41 9500 MATD 9500 XT MANUAL ...
Page 45: ...Page 42 9500 Control Valve Assembly MATD 9500 XT MANUAL ...
Page 46: ...Page 43 Second Tank Assemblies MATD 9500 XT MANUAL ...
Page 47: ...Page 44 Second Tank Assemblies MATD 9500 XT MANUAL ...
Page 48: ...Page 45 Meter Assemblies MATD 9500 XT MANUAL ...
Page 49: ...Page 46 Meter Assemblies MATD 9500 XT MANUAL ...
Page 50: ...Page 47 3 4 1 or 1 1 2 Paddle Wheel Meter Cap Assembly MATD 9500 XT MANUAL ...
Page 51: ...Page 48 Brine Valve Systems 1600 and 1700 Series MATD 9500 XT MANUAL ...
Page 52: ...Page 49 9500 2350 Safety Brine Valve MATD 9500 XT MANUAL ...
Page 53: ...Page 50 ...
Page 54: ...Page 51 Troubleshooting MATD 9500 XT MANUAL ...