HYDRONIC OPERATION TROUBLESHOOTING
Fault
Possible Cause
Verification
Recommended Action
High Discharge
Pressure
Aquastat set too high.
Verify aquastat setting.
Lower aquastat setting to recom-
mended value of
115°F (46°C).
Low or no Indoor loop flow.
Delta T across the Indoor Loop ports
should be 8-12°F (3-6°C), or compare
pressure drop to the tables for the unit.
Verify pump is working and sized
correctly. Check for restrictions in
the circuit, e.g. valve partially closed.
TXV adjusted too far closed. Verify superheat. It should be between
8-12°F (3-6°C). Superheat will be high if
TXV is closed too far.
Adjust TXV to obtain 8-12°F (3-6°C)
superheat.
TXV stuck almost closed or
partially blocked by foreign
object.
Adjusting the TXV does not affect the
superheat or the suction pressure.
Adjust the TXV all the way in and out
a few times to loosen it. Replace
TXV if this does not work.
Filter-dryer plugged
Feel each end of the filter-dryer: it
should be the same temperature. If
there is a temperature difference then it
is plugged. Also causes low suction
pressure.
Replace filter-dryer.
Unit is overcharged.
(Only possible if unit has
been serviced in the field and
incorrectly charged.)
High sub-cooling, low delta T across air
coil.
Remove 1/2lb of refrigerant at a time
and verify that the discharge pres-
sure reduces.
Faulty 4-way (condenser
select) valve or actuator.
Verify actuator rotates 90 degrees over
~80 seconds when unit is switched from
air heating to hydronic heating modes.
Replace valve or actuator if faulty.
Low Suction
Pressure
Low or no outdoor liquid flow. Delta T across the Outdoor Loop ports
should be between 5-7°F (3-4°C), or
compare pressure drop to the tables for
the unit.
Determine the cause of the flow re-
striction and correct it.
Verify pumps are working and sized
correctly for ground loop systems.
Verify well pump and water valve are
working for ground water systems.
Entering liquid temperature
too cold.
Measure the entering liquid temperature.
Most likely caused by undersized ground
loop.
Increase the size of the ground loop.
Dirty or fouled coaxial heat
exchanger (more likely for
open loop, unlikely for ground
loop)
Disconnect the water lines and check
the inside of the pipes for scale deposits.
Backflush the coaxial exchanger with
a calcium-removing cleaning solution.
Indoor loop entering liquid
temperature too cold
Measure temperature. Should be above
60°F (15°C).
Restrict Indoor liquid flow temporarily
until buffer tank comes up to temper-
ature.
Summary of Contents for TF-45
Page 12: ...Page 12 001223MAN 05 1 Jul 2017 ...
Page 13: ...1 Jul 2017 Page 13 001223MAN 05 ...
Page 14: ...Page 14 001223MAN 05 1 Jul 2017 ...
Page 15: ...1 Jul 2017 Page 15 001223MAN 05 ...
Page 16: ...Page 16 001223MAN 05 1 Jul 2017 ...
Page 19: ...1 Jul 2017 Page 19 001223MAN 05 ...
Page 20: ...Page 20 001223MAN 05 1 Jul 2017 ...
Page 23: ...1 Jul 2017 Page 23 001223MAN 05 ...
Page 24: ...Page 24 001223MAN 05 1 Jul 2017 ...
Page 25: ...1 Jul 2017 Page 25 001223MAN 05 ...
Page 26: ...Page 26 001223MAN 05 1 Jul 2017 ...
Page 27: ...1 Jul 2017 Page 27 001223MAN 05 ...
Page 30: ...Page 30 001223MAN 05 1 Jul 2017 ...
Page 31: ...1 Jul 2017 Page 31 001223MAN 05 ...
Page 32: ...Page 32 001223MAN 05 1 Jul 2017 ...
Page 33: ...1 Jul 2017 Page 33 001223MAN 05 ...
Page 34: ...Page 34 001223MAN 05 1 Jul 2017 ...
Page 38: ...Page 38 001223MAN 05 1 Jul 2017 ...
Page 39: ...1 Jul 2017 Page 39 001223MAN 05 ...
Page 40: ...Page 40 001223MAN 05 1 Jul 2017 ...
Page 74: ...Page 74 001223MAN 05 1 Jul 2017 Wiring Diagram 208 230 1 60 ...
Page 75: ...1 Jul 2017 Page 75 001223MAN 05 Electrical Box Layout 208 230 1 60 ...
Page 76: ...Page 76 001223MAN 05 1 Jul 2017 Wiring Diagram 208 3 60 ...
Page 77: ...1 Jul 2017 Page 77 001223MAN 05 Electrical Box Layout 208 3 60 ...
Page 78: ...Page 78 001223MAN 05 1 Jul 2017 Wiring Diagram 460 3 60 ...
Page 79: ...1 Jul 2017 Page 79 001223MAN 05 Electrical Box Layout 460 3 60 ...
Page 80: ...Page 80 001223MAN 05 1 Jul 2017 Wiring Diagram 220 1 50 ...
Page 81: ...1 Jul 2017 Page 81 001223MAN 05 Electrical Box Layout 220 1 50 ...
Page 82: ...Page 82 001223MAN 05 1 Jul 2017 ...
Page 83: ...1 Jul 2017 Page 83 001223MAN 05 ...
Page 84: ...Page 84 001223MAN 05 1 Jul 2017 ...
Page 85: ...1 Jul 2017 Page 85 001223MAN 05 Dimensions TF 45 Left Return ...
Page 86: ...Page 86 001223MAN 05 1 Jul 2017 Dimensions TF 45 Right Return ...
Page 87: ...1 Jul 2017 Page 87 001223MAN 05 Dimensions TF 55 65 75 80 Left Return ...
Page 88: ...Page 88 001223MAN 05 1 Jul 2017 Dimensions TF 55 65 75 80 Right Return ...