FAULT CODE TROUBLESHOOTING
Fault
Possible Cause
Verification
Recommended Action
Fault Code 1
(High Pressure
Control)
High operating refrigerant
pressure
Using a refrigeration gauge set, verify
that high pressure approaches or ex-
ceeds 565psi with compressor on.
See “High Discharge Pressure” in
Heating Mode / Cooling Mode Trou-
bleshooting section.
Faulty High Pressure Control
(open).
* For this test there must be a
signal present on Y1, but
compressor should not be
running (disconnect com-
pressor power plug).
Verify that there is 24VAC across HPS
(right terminal) on the control board and
C of the terminal strip, as well as HPS
(left terminal) and C.
Replace high pressure control if volt-
age is present on one terminal but
not the other.
Faulty control board.
24VAC is present across HPS (right ter-
minal) and C of the terminal strip, as well
as HPS (left terminal) and C, but is not
present across CC on the control board
and C after 10 minutes.
Replace control board.
Fault Code 2
(Low Pressure
Control)
Low operating refrigerant
pressure
Using a refrigeration gauge set, verify
that low pressure approaches or dips
below 55psi (ground loop) or 75 psi
(open loop) with compressor on.
See “Low Discharge Pressure” in
Heating Mode / Cooling Mode Trou-
bleshooting section.
Faulty Low pressure control
(open).
* For this test there must be a
signal present on Y1, but
compressor should not be
running (disconnect com-
pressor power plug).
Verify if there is 24VAC across LPS on
the control board and C of the terminal
strip, as well as HPS (left terminal) and
C.
Replace high pressure control if volt-
age is present on one terminal but
not the other.
Faulty control board.
24VAC is present across LPS and C of
the terminal strip, as well as HPS (left
terminal) and C, but is not present
across CC on the control board and C
after 10 minutes.
Replace control board.
Little or no refrigerant in unit. With compressor off, use a refrigeration
gauge set to check refrigeration pres-
sure of the unit for a very low value (less
than 100 psi).
Locate the leak and repair it. Spray
9, a sniffer, and dye are common
methods of locating a leak.
Fault Code 4
(Condensate
overflow)
Condensate overflow.
Drip tray under air coil is full of water up
to the terminals of the condensate sen-
sor.
Locate blockage or other cause of
drain problem and rectify.
Fault Code 5
(Brownout)
Low voltage from the electri-
cal grid.
Verify that the electrical supply has
dropped below ~165VAC, causing trans-
former voltage to drop below 18VAC.
Contact electrical utility or wait for
regular service to be restored.
THERMOSTAT TROUBLESHOOTING
Fault
Possible Cause
Verification
Recommended Action
No Y1 signal to
heat pump
(after 6 minutes)
Incorrect thermostat setup.
Thermostat does not indicate a call for
heat. No 24VAC signal present across
Y1 & C of the thermostat
Correct the setup.
Faulty thermostat to heat
pump wiring.
24VAC signal present across Y1 & C of
the thermostat but not present across Y1
& C of the terminal strip.
Correct or replace wiring
Faulty thermostat.
No 24VAC between Y1 & C of the ther-
mostat when a call is indicated.
Replace thermostat.
Summary of Contents for TF-45
Page 12: ...Page 12 001223MAN 05 1 Jul 2017 ...
Page 13: ...1 Jul 2017 Page 13 001223MAN 05 ...
Page 14: ...Page 14 001223MAN 05 1 Jul 2017 ...
Page 15: ...1 Jul 2017 Page 15 001223MAN 05 ...
Page 16: ...Page 16 001223MAN 05 1 Jul 2017 ...
Page 19: ...1 Jul 2017 Page 19 001223MAN 05 ...
Page 20: ...Page 20 001223MAN 05 1 Jul 2017 ...
Page 23: ...1 Jul 2017 Page 23 001223MAN 05 ...
Page 24: ...Page 24 001223MAN 05 1 Jul 2017 ...
Page 25: ...1 Jul 2017 Page 25 001223MAN 05 ...
Page 26: ...Page 26 001223MAN 05 1 Jul 2017 ...
Page 27: ...1 Jul 2017 Page 27 001223MAN 05 ...
Page 30: ...Page 30 001223MAN 05 1 Jul 2017 ...
Page 31: ...1 Jul 2017 Page 31 001223MAN 05 ...
Page 32: ...Page 32 001223MAN 05 1 Jul 2017 ...
Page 33: ...1 Jul 2017 Page 33 001223MAN 05 ...
Page 34: ...Page 34 001223MAN 05 1 Jul 2017 ...
Page 38: ...Page 38 001223MAN 05 1 Jul 2017 ...
Page 39: ...1 Jul 2017 Page 39 001223MAN 05 ...
Page 40: ...Page 40 001223MAN 05 1 Jul 2017 ...
Page 74: ...Page 74 001223MAN 05 1 Jul 2017 Wiring Diagram 208 230 1 60 ...
Page 75: ...1 Jul 2017 Page 75 001223MAN 05 Electrical Box Layout 208 230 1 60 ...
Page 76: ...Page 76 001223MAN 05 1 Jul 2017 Wiring Diagram 208 3 60 ...
Page 77: ...1 Jul 2017 Page 77 001223MAN 05 Electrical Box Layout 208 3 60 ...
Page 78: ...Page 78 001223MAN 05 1 Jul 2017 Wiring Diagram 460 3 60 ...
Page 79: ...1 Jul 2017 Page 79 001223MAN 05 Electrical Box Layout 460 3 60 ...
Page 80: ...Page 80 001223MAN 05 1 Jul 2017 Wiring Diagram 220 1 50 ...
Page 81: ...1 Jul 2017 Page 81 001223MAN 05 Electrical Box Layout 220 1 50 ...
Page 82: ...Page 82 001223MAN 05 1 Jul 2017 ...
Page 83: ...1 Jul 2017 Page 83 001223MAN 05 ...
Page 84: ...Page 84 001223MAN 05 1 Jul 2017 ...
Page 85: ...1 Jul 2017 Page 85 001223MAN 05 Dimensions TF 45 Left Return ...
Page 86: ...Page 86 001223MAN 05 1 Jul 2017 Dimensions TF 45 Right Return ...
Page 87: ...1 Jul 2017 Page 87 001223MAN 05 Dimensions TF 55 65 75 80 Left Return ...
Page 88: ...Page 88 001223MAN 05 1 Jul 2017 Dimensions TF 55 65 75 80 Right Return ...