1-Jun-2018
Page 67
002000MAN-01
INDOOR FAN/BLOWER TROUBLESHOOTING
Fault
Possible Cause
Verification
Recommended Action
Low indoor
airflow
Dirty air filter.
Inspect.
Replace.
Dirty air coil.
Inspect.
Clean.
Poor ductwork.
Measure delta T between supply
and return ducts at the unit. In
heating mode, it should not be
above 30°F(17°C).
The ECM fan will provide proper
airflow up to 0.5 inH2o for 1/2HP
motors and 0.7 inH2o for 1HP
motors. The ductwork is poorly
designed or greatly undersized if
the fan motor cannot provide the
required airflow.
Airflow selected is too low. Check airflow settings on Indoor Fan
page of the PC APP.
Select a higher setting.
Airflow reduction is ena-
bled.
AR1 and AR2 are connected with a
dry contact or jumper.
Airflow reduction may not be fea-
sible with lower airflow selections.
Increase settings until unit oper-
ates properly.
Indoor fan not
operating at cor-
rect speeds.
Wrong model size
selected.
Verify that the model size is correct
on the Configuration Page of the PC
APP.
Select the correct model size.
Indoor fan not
operating or op-
erating intermit-
tently
Fan control signal harness
and/or fan power harness
is loose.
Verify that the connector is properly
inserted into the fan motor. Gently
tug on each wire to verify it is
properly inserted into the connector.
Repair any loose connections.
Control board not config-
ured properly.
Verify that the model series is cor-
rect on the Configuration Page of
the PC APP.
Correct the configuration. If the
wrong series is selected there
may be not be any fan output.
Faulty fan power harness
or faulty motor.
Insert the tips of the voltmeter
probes into the back of the connect-
or at the fan to measure the voltage
across the red and black wires.
Value should be ~230VAC.
Replace power harness if
230VAC is not present, replace
motor if 230VAC is present.
Faulty control board out-
puts.
Note: cycle the power
once to see if the fan
begins operating
properly first.
Create a call for the fan from the
thermostat (24VAC on G terminal in
heat pump).
On the ECM Fan connector on the
left side of the control board:
1) verify that there is 12 to 20VDC
between pin G (grey wire) and
pin C (white wire).
2) Verify that there is 2 to 6VDC
between pin P (dark green wire)
and pin C (white wire)
If there is no voltage present on
either of the pins (G and P) re-
place the control board.
Ensure control board model se-
ries is correct, see above.
Faulty control signal har-
ness or faulty motor head.
Create a call for the fan from the
thermostat (24VAC on G terminal in
heat pump).
On the ECM Fan connector at the
fan motor:
1) verify that there is 12 to 20VDC
between pin G (grey wire) and
pin C (white wire).
2) Verify that there is 2 to 6VDC
between pin P (dark green wire)
and pin C (white wire)
If proper signal isn’t present, re-
place the fan control signal har-
ness. If proper signal is present,
replace fan motor.
Summary of Contents for ATF-45
Page 12: ...Page 12 002000MAN 01 1 Jun 2018...
Page 15: ...1 Jun 2018 Page 15 002000MAN 01...
Page 16: ...Page 16 002000MAN 01 1 Jun 2018...
Page 17: ...1 Jun 2018 Page 17 002000MAN 01...
Page 18: ...Page 18 002000MAN 01 1 Jun 2018...
Page 20: ...Page 20 002000MAN 01 1 Jun 2018...
Page 21: ...1 Jun 2018 Page 21 002000MAN 01...
Page 22: ...Page 22 002000MAN 01 1 Jun 2018...
Page 23: ...1 Jun 2018 Page 23 002000MAN 01...
Page 24: ...Page 24 002000MAN 01 1 Jun 2018...
Page 25: ...1 Jun 2018 Page 25 002000MAN 01...
Page 27: ...1 Jun 2018 Page 27 002000MAN 01...
Page 31: ...1 Jun 2018 Page 31 002000MAN 01...
Page 84: ...Page 84 002000MAN 01 1 Jun 2018 Wiring Diagram 208 230 1 60...
Page 85: ...1 Jun 2018 Page 85 002000MAN 01 Electrical Box Layout 208 230 1 60...
Page 86: ...Page 86 002000MAN 01 1 Jun 2018 Wiring Diagram 208 3 60...
Page 87: ...1 Jun 2018 Page 87 002000MAN 01 Electrical Box Layout 208 3 60...
Page 88: ...Page 88 002000MAN 01 1 Jun 2018 Wiring Diagram 460 3 60...
Page 89: ...1 Jun 2018 Page 89 002000MAN 01 Electrical Box Layout 460 3 60...
Page 90: ...Page 90 002000MAN 01 1 Jun 2018 ACE 45 55 Wiring Diagram ACE 65 75 Wiring Diagram...
Page 91: ...1 Jun 2018 Page 91 002000MAN 01...
Page 92: ...Page 92 002000MAN 01 1 Jun 2018...
Page 93: ...1 Jun 2018 Page 93 002000MAN 01...
Page 94: ...Page 94 002000MAN 01 1 Jun 2018 Dimensions ATF 45 Left Return INDOOR UNIT OUTDOOR UNIT ACE 45...
Page 95: ...1 Jun 2018 Page 95 002000MAN 01 INDOOR UNIT OUTDOOR UNIT ACE 45 Dimensions ATF 45 Right Return...
Page 96: ...Page 96 002000MAN 01 1 Jun 2018 INDOOR UNIT OUTDOOR UNIT ACE 55 Dimensions ATF 55 Left Return...
Page 97: ...1 Jun 2018 Page 97 002000MAN 01 INDOOR UNIT OUTDOOR UNIT ACE 55 Dimensions ATF 55 Right Return...
Page 100: ...Page 100 002000MAN 01 1 Jun 2018 ACE 65 75 ACE 45 55...