BOARD FAULTS Tab:
This tab shows hardware faults that could occur. If one of these faults occurs there may be a problem with the control board hardware
or with the LCD Display and buttons.
NOTE: If a Board Fault occurs, try cycling the power to the heat pump. Turn the power off for 10 seconds and then back on
again. If the fault persists then there is most likely a problem with the hardware and the board will need to be
replaced.
Digital Inputs:
A failure has occurred and the Control Board may no longer respond to the digital input signals.
Digital Outputs:
A failure has occurred and the digital outputs may no longer work properly.
PWM Outputs:
A failure has occurred and the PWM / 0-10VDC outputs may no longer work properly.
Analog to Digital:
A failure has occurred and the data from the A/D converter may be corrupt resulting in erratic data values.
Real Time Clock:
A failure has occurred, system time / date may no longer be valid, all time stamped data may be corrupt.
Flash Memory:
A failure has occurred stored data may be corrupt. It may be possible to correct this by using the menu item
Tools—Reset to Factory Defaults
. If this clears the fault then the system configuration will have to be setup
again.
Menu Buttons:
A failure has occurred and the Control board may no longer respond to menu button keypresses. Try turning off the
power, disconnecting and reconnecting the cable between the LDC Display board and the Control Board and then
turning the power back on again. If this does not work then either the LDC Display board, the cable or the driver
section of the Control Board may be faulty.
LCD Display:
A failure has occurred and display may show erratic data, no data or may not turn on at all. Try turning off the
power, disconnecting and reconnecting the cable between the LDC Display board and the Control Board and then
turning the power back on again. If this does not work then either the LDC Display board, the cable or the driver
section of the Control Board may be faulty.
Temperature Sensors:
A failure has occurred or the sensor is disconnected. Greyed out sensors do not to apply to the
system as configured. Some sensors may be optional, go to the Configuration Page to enable/disable them.
IMPORTANT NOTES:
The heat pump will not operate if the Outdoor Ambient probe (HTS) is faulty or disconnected. The
auxiliary will continue to operate but it’s sepoint value may be reduced if using the Outdoor Reset function.
If the Indoor OUT (I_OUT) probe is faulty or disconnected, neither the heat pump nor the auxiliary will operate
if using Setpoint Control. They will continue to operate under Signals or BACnet control.
Fault Indicators
Greyed out do not apply.
Summary of Contents for ATF-45
Page 12: ...Page 12 002000MAN 01 1 Jun 2018...
Page 15: ...1 Jun 2018 Page 15 002000MAN 01...
Page 16: ...Page 16 002000MAN 01 1 Jun 2018...
Page 17: ...1 Jun 2018 Page 17 002000MAN 01...
Page 18: ...Page 18 002000MAN 01 1 Jun 2018...
Page 20: ...Page 20 002000MAN 01 1 Jun 2018...
Page 21: ...1 Jun 2018 Page 21 002000MAN 01...
Page 22: ...Page 22 002000MAN 01 1 Jun 2018...
Page 23: ...1 Jun 2018 Page 23 002000MAN 01...
Page 24: ...Page 24 002000MAN 01 1 Jun 2018...
Page 25: ...1 Jun 2018 Page 25 002000MAN 01...
Page 27: ...1 Jun 2018 Page 27 002000MAN 01...
Page 31: ...1 Jun 2018 Page 31 002000MAN 01...
Page 84: ...Page 84 002000MAN 01 1 Jun 2018 Wiring Diagram 208 230 1 60...
Page 85: ...1 Jun 2018 Page 85 002000MAN 01 Electrical Box Layout 208 230 1 60...
Page 86: ...Page 86 002000MAN 01 1 Jun 2018 Wiring Diagram 208 3 60...
Page 87: ...1 Jun 2018 Page 87 002000MAN 01 Electrical Box Layout 208 3 60...
Page 88: ...Page 88 002000MAN 01 1 Jun 2018 Wiring Diagram 460 3 60...
Page 89: ...1 Jun 2018 Page 89 002000MAN 01 Electrical Box Layout 460 3 60...
Page 90: ...Page 90 002000MAN 01 1 Jun 2018 ACE 45 55 Wiring Diagram ACE 65 75 Wiring Diagram...
Page 91: ...1 Jun 2018 Page 91 002000MAN 01...
Page 92: ...Page 92 002000MAN 01 1 Jun 2018...
Page 93: ...1 Jun 2018 Page 93 002000MAN 01...
Page 94: ...Page 94 002000MAN 01 1 Jun 2018 Dimensions ATF 45 Left Return INDOOR UNIT OUTDOOR UNIT ACE 45...
Page 95: ...1 Jun 2018 Page 95 002000MAN 01 INDOOR UNIT OUTDOOR UNIT ACE 45 Dimensions ATF 45 Right Return...
Page 96: ...Page 96 002000MAN 01 1 Jun 2018 INDOOR UNIT OUTDOOR UNIT ACE 55 Dimensions ATF 55 Left Return...
Page 97: ...1 Jun 2018 Page 97 002000MAN 01 INDOOR UNIT OUTDOOR UNIT ACE 55 Dimensions ATF 55 Right Return...
Page 100: ...Page 100 002000MAN 01 1 Jun 2018 ACE 65 75 ACE 45 55...