Mantracourt Electronics Limited
T24 Technical Manual
27
CalPoint1
80
The % full scale value of this calibration point.
FLOAT
RW
CalPoint2
81
The % full scale value of this calibration point.
FLOAT
RW
CalPoint3
82
The % full scale value of this calibration point.
FLOAT
RW
CalPoint4
83
The % full scale value of this calibration point.
FLOAT
RW
CalPoint5
84
The % full scale value of this calibration point.
FLOAT
RW
CalPoint6
85
The % full scale value of this calibration point.
FLOAT
RW
CalPoint7
86
The % full scale value of this calibration point.
FLOAT
RW
CalPoint8
87
The % full scale value of this calibration point.
FLOAT
RW
CalPoint9
88
The % full scale value of this calibration point.
FLOAT
RW
CalPointGain1
89
The gain to apply to the input at this calibration point. FLOAT
RW
CalPointGain
90
The gain to apply to the input at this calibration point. FLOAT
RW
CalPointGain
91
The gain to apply to the input at this calibration point. FLOAT
RW
CalPointGain
92
The gain to apply to the input at this calibration point. FLOAT
RW
CalPointGain
93
The gain to apply to the input at this calibration point. FLOAT
RW
CalPointGain
94
The gain to apply to the input at this calibration point. FLOAT
RW
CalPointGain
95
The gain to apply to the input at this calibration point. FLOAT
RW
CalPointGain
96
The gain to apply to the input at this calibration point. FLOAT
RW
CalPointGain
97
The gain to apply to the input at this calibration point. FLOAT
RW
CalPointOffset1
98
The offset to apply to the input at this calibration
point.
FLOAT
RW
CalPointOffset2
99
The offset to apply to the input at this calibration
point.
FLOAT
RW
CalPointOffset3
100
The offset to apply to the input at this calibration
point.
FLOAT
RW
CalPointOffset4
101
The offset to apply to the input at this calibration
point.
FLOAT
RW
CalPointOffset5
102
The offset to apply to the input at this calibration
point.
FLOAT
RW
CalPointOffset6
103
The offset to apply to the input at this calibration
point.
FLOAT
RW
CalPointOffset7
104
The offset to apply to the input at this calibration
point.
FLOAT
RW
CalPointOffset8
105
The offset to apply to the input at this calibration
point.
FLOAT
RW
CalPointOffset9
106
The offset to apply to the input at this calibration
point.
FLOAT
RW
Value
72
Reads the user calibrated output.
FLOAT
R
Counts
70
Raw A/D counts
INT32
R
PFS
71
Factory calibrated percent full scale (0=0V, 100=10V)
FLOAT
R
DigitalOut
108
Read or set the digital output state.
Value
Definition
0
Turn digital output off
1
Turn digital output on
2
Make digital output mirror the LED
state (V1.05 and later)
FLOAT
RW
Status
74
Live status where the bit values indicate status. The
following table shows the decimal bit values and their
meaning.
Bit Value
Definition
1
STATUS_SHUNT_CAL
2
STATUS_INPUT_INTEGRITY
4
Reserved
8
Reserved
16
STATUS_POWER_UP
32
STATUS_BATT_LOW
64
STATUS_DIGITAL_INPUT
128
STATUS_DIGITAL_OUTPUT
Reset
54
Restarts the device and utilises new channel and
encryption keys if those have been changed and saved.
Command