57
Prior to commissioning the dampers and during subsequent serviceability checks, all versions,
including electrical component operation, must be inspected and functionally tested. After commis-
sioning, serviceability checks must be performed at least twice annually. If no defect is found during
two consecutive serviceability checks, then it's possible to perform serviceability checks once yearly.
The results of regular inspections, deficiencies found and all-important facts concerning the
dampers function must be entered in the "FIRE BOOK" and immediately reported to the operator.
If, for any reason, the dampers are found unfit to perform their function, this must be clearly indicated.
The operator is obliged to ensure that the damper is brought into a state where it will be able to
perform its function again and during this time must provide fire protection in another sufficient way.
Spare parts are only delivered on order.
These checks must be carried out before the dampers are put into operation and during subsequent
serviceability checks.
Visual inspection of the damper's correct installation, the damper's internal space, the damper
blades, the bearing surfaces of the blades and the silicone seal.
Check the adjustment of the damper blade from the open position to the closed position and back.
The data label is attached to the damper body.
WEIGHT (kg):
Dobříšská 550, 267 24 Hostomice, Czech Republic
MANDÍK, a.s.
ACTUATING SYSTEM:
YEAR/SER.NO.:
DIMENSION:
1391
TPM 146/20
R
FIRE PROTEC. CLASS:
MANUAL
Cert. No.: 1391-CPR-2021/0009, DoP: PM/SEDM-L/01/22/1
EN 12101-8:2011