background image

 

 

  

                                                        
 
 
 
 
 
 
 

 

 

 

 

 

 

Smoke Shield PTC - 'E S' 

RATED FIRE DAMPER

 

(Fire & Smoke barrier) 

Installation, Operating & Maintenance Instructions

 

 

 

www.actionair.co.uk 

For clarity, damper not shown installed in 
supporting wall construction, please refer 
to the Actionair approved Fire and Smoke 
Dampers Installation Manual. The latest 
version can be found on our website: 
www.actionair.co.uk 

Health and Safety                       

 

All wiring should be carried out in accordance with the wiring details provided, the IEE and BS regulations, by a competent person. 
Care must be taken when installing and inspecting dampers, as they are likely to close without warning due to loss of electrical 
power, or a temperature rise in the ductwork. This is their prime function.  
Do not introduce any items, fingers or limbs between the blades. 
Larger dampers are heavy and must be handled in accordance with current regulations and good practice. 

July 2013

 

SmokeShield PTC Damper Control Modes

Control Mode Installation Procedure 

 

Remove transit plate and recycle. 

 

Slide the interface and mode assembly into the shroud, ensuring that the 
slots in the interface casing and the drive coupling, located on the rear of the 
interface, are in line. 
Push the assembly fully home until the interface sprung retaining pin 
engages through the locating hole in the damper shroud (

snap

lock™).  

 

The control mode can be fitted in any of three orientations i.e. Vertically 
down, Horizontally and Vertically up, if you have an space  restrictions. This 
can easily be carried out by; 

 

Remove and retain the screw (8mm A/F) and washer, through the 
position indicator on the control mode. 

 

Remove the control mode and location plate. 

 

Taking care not to disturb the drive hexagon, replace the location 
plate, and control mode in the new orientation. 

 

Replace the washer and screw tight (Max 5Nm) 

 

Select a suitable position for the Electrical Thermal Release (ETR)  
to be mounted through the ductwork. Ideally this should be in the top half of 
the duct and/or above the level of the interface. 
Apply the self-adhesive template (located on the rear of the ETR) and drill 
the necessary holes (Ø3mm & Ø9.5...Ø11mm).

 

 

Push the ETR through the duct and ensure that both screws are used to 
hold it in position. Both screws should be tightened fully to ensure that both 
sections of the ETR are closed together. This is a safety feature and should 
both sections not be closed the unit will not operate. 
For ductless installations the ETR should be fitted onto the damper spigot 
(not casing) above the damper interface shroud, and in accordance with the 
fitting instructions. 

 

If the ETR is not fitted in the exact manner described above, the unit 
will not operate. 

 

The damper should be manually reset and released using the winder 
provided, to ensure that correct mechanical operation is achievable. 
It is possible to mechanically lock open the SmokeShield PTC damper to 
allow air to pass through it by using the winder provided. This may be 
necessary if electrical power is not yet available. However, the ETR is not 
operable in this instance and the damper will not release automatically 
should the temperature rise or a fire occur. 

 

The unit must be wired as detailed. 

When power is available, the unit must be checked for correct 
electrical operation. Power on to reset, power off to release. 

The unit must also be checked by pushing and holding the test switch on the 
ETR to confirm that the damper releases. When pressure is removed from 
the switch, the damper resets. This may also be done after the initial 
installation test, to provide periodic operation of the damper to simulate 
actual fail-safe release under smoke/fire conditions. 

 

The ETR cable must not cut to shorten or lengthen, and care must be taken 
not to damage it. Either will render the unit inoperable and void any 
warranties. This is due to a built in safety feature. 

 

0832-CPR-P0002

Summary of Contents for SmokeShield PTC

Page 1: ...ion for the Electrical Thermal Release ETR to be mounted through the ductwork Ideally this should be in the top half of the duct and or above the level of the interface Apply the self adhesive template located on the rear of the ETR and drill the necessary holes Ø3mm Ø9 5 Ø11mm Push the ETR through the duct and ensure that both screws are used to hold it in position Both screws should be tightened...

Page 2: ...TF 72 C AC 250V 6 3 A BROWN BLUE 1 2 3 4 5 6 L1 SUPPLY 230V AC 50 60Hz TYPICALLY 12W MOTORING 4W RESET COMMON COMMON VOLT FREE CONTACT MADE BETWEEN 1 2 WHEN DAMPER FULLY RELEASED VOLT FREE CONTACT MADE BETWEEN 4 6 WHEN DAMPER FULLY RESET M AC DC 24V 50 60 Hz 14 VA 12 4 W 30 C 50 C CONTINUOUS ELECTRICAL THERMAL RELEASE ETR MUST BE FITTED TO DUCTING FOR DAMPER OPERATION SPRING BIASED TEST SWITCH TF ...

Page 3: ...010 SMOKE SHIELD PTC LEAKAGE RATED SS I F E120 ve ho i o S SS DWFX C SS DWFX F SS OSW E120 ve i o S SS S A E120 ve i o S E120 ho i o E90 ho i o S Sensing element Response temperature 72 C Load Bearing capacity N A Closure times M5 6 22s tamb 20 C M5 3P 16s tamb 20 C Corrosion tested to En 60068 2 52 Pass Operational reliability 20 000 cycles Pass Ambient leakage test Pass LPS 1162 Issue 4 Cert No ...

Page 4: ...ot over tighten The mode is incorrectly wired Check wiring in accordance with procedures The ETR cables have been damaged or tampered with Replace with new mode Control Mode operates but limited or no movement of damper blades is observed The mode is not correctly synchronised with the interface Remove motor from interface Check motor in fully released state Set position of interface and refit mot...

Reviews:

Related manuals for SmokeShield PTC