62
Position:
1
Fire damper
2
Installation frame E1
3
Holder (including in installation
frame E1 packing)
4
Fire resistant board
5
Screw
6
Additional fire resistant board
7
Fire resistant foam tape
Used materials - example:*
4
Glasroc F Ridurit th. 20 mm
5
Screw Ridurit
6
Glasroc F Ridurit th. 20 mm
7
Promaseal XT
Dimensions
Number
ZB1
Number
ZH1
A,B ≤ 400
1
1
400 <
A,B ≤ 800
2
2
800 <
B ≤ 1200
3
3
1200 <
B ≤ 1500
4
4
≥
100
≤
250
50
≤
250
50
20
20
80
* It is alternatively possible to use Knauf or Promat solution.
Gap between frame and thin shaft wall construction must be filled by glue (PROMAT K84).
Dampers has to be suspended in an appropriate manner see chapter 9.
It is possible to use
corresponding number
of holes and screws