11
Design .61 with communication and supply device can be complemented with smoke detector
ORS 142 K. For supply and comunnication is used BKN 230-24-C-MP, which together with the
BF 24TN-ST (BFL 24T-ST, BFN 24T-ST ) enables central control and checks of fire damper by
means of a simple 2-conductor wiring and it also allows connection to the system via MP-BUS
communication. More information in the Belimo catalog.
Nominal voltage
AC 230 V 50/60Hz
Power consumption
3,5 W (operating position)
Dimensioning
10 VA (including actuating mechanism with spring return)
Protection Class
II
Degree of protection
IP 40
Ambient temperature
Non-operating temperature
-20°C … +50°C
-40°C … +80°C
Connection - net
- motor
- terminal board
cable 0,9 m with EURO plug type 26
6-pole connector, 3-pole connector
screw terminals for cable 2x1,5 mm
²
External smoke detector, +24 V, max. 50 mA
External smoke detector, control input
Connection of more BKN devices as slaves
GND
MP-BUS
a
b
1
2
3
4
5
6
7
BAT
1
2
3
4
5
6
7
b
a
1)
1)
2)
BAT
1) Bridge has been installed by the manufacturer. If needed, it can be
removed ad replaced with a thermoelectric starting mechanism. If
terminals 1 and 2 are not interconnected, safety function is initiated.
2) Bridge can be used only for starting and without BKS24… !
Two conductor wiring to BKS24