8.1 Warning Light Sequence
8.2 Programming warning lights sequence (door should be in the closed position)
NOTE:
Warning lights is functional only with Timer to Close
8.3 Connection of Red and Green warning lights
(If Warning Lights Module is sold separately)
Lights
Operating sequence
Red
The light is solid red when the door is closing and opening. Light turns OFF once the door
reaches the fully open or fully closed position
Green
The green light is ON only when the door is fully open and stays ON during a preset time
(programmed by the Timer to Close)
Red
(flashing)
The red light starts flashing once the green light is OFF and when the door is about to close. This is
to warn the users that the door will close shortly. It stops flashing once the door start closing.
Warning lights sequence is operational from Mid-Point position in same way as from fully open
SETTING
ACTIVATE
DEACTIVATE
SELECT
SWITCH
TIMER TO
CLOSE
Set select switch on “B”
Press “Open” button to add 15 sec or
“Close” button to add 1 sec each time
(max. 4 minutes & 30 seconds)
Set the select switch on T or TS mode
Set select switch on “B”
Press “Stop” button the timer to close
is reset to 0 sec but still is activated.
To deactivate the timer to close
completely set the switch on desired
position (0, 1, 2 or 3)
RED
LIGHTS
(Flashing
Time)
Default time setting 5 sec
Set select switch on “8”
Press “Open” to add 1 sec each time to
a maximum of 15 sec.
Press “Close” to deduct 1 sec each time
to a minimum of 0 sec.
Press “Stop” to bring the flashing time
to 5 sec by default
Set select switch on “8” and press
“Close” to bring the flashing time to 0
sec.
Or set the select switch to desired
position (0, 1, 2 or 3)
EC
B
Warning lights
Module
TB5
L
/L1
N/L1
L3
TB3
Fix the warning lights module in the control box
so that it doesn’t touch to any metal parts
Red
B
lac
k
G
ree
n
For 3PH applications only, an
appropriate transformer (mini
100VAC) should be used
TRANSFORMER
208/460/575V
– 115V
To “Warning Light
Module” #L & #N
From any two incoming
lines of the 3PH supply
115V
Red
Green
Red
Green
TIMER TO
CLOSE
D
A
B
C
9
8
F
E
0
4
6
5
7
2
1
3
WARNING
(OPTION)
LIGHT
TIMER
C
D
B
A
9
8
F
E
0
5
6
7
2
1
4
3
Summary of Contents for Opera-GH
Page 18: ...18 6 Opera GH exploded view...
Page 29: ...29 7 10 Single phase ECB wiring diagram...
Page 30: ...30 7 11 3 Phase ECB wiring diagram...
Page 42: ...42 9 9 Single phase Hardwired wiring diagram...
Page 43: ...43 9 10 3 phase Hardwired wiring 10 3 phase Hardwired wiring diagram...
Page 45: ...45 NOTES...
Page 46: ...46 NOTES...
Page 47: ...47 NOTES...
Page 48: ...48 BOOK146 REV 1 2007 02 19...