23
7.2 ELECTRONIC CONTROL BOARD
LED MONITORING STATUS
LED’s on the ECB help will wiring and making troubleshooting diagnoses. Every LED states the actual position
of the door. The board has a non-volatile memory and all the LED return to their initial state after a power
interruption.
WRONG HANDLING
Wrong handling protection prevents the operator from over passing the limits when incoming 3-phase power or
a single-phase motor are incorrectly connected.
When the operator turns in the opposite direction and reaches the wrong limit switch, the LED indicator
flashes-on and all the external commands are ignored by the electronic board.
To correct the problem when:
Stop LED OFF:
Check if the Stop button is properly connected on #8 and #9 or if a Normally Closed contact is used.
Verify if the Hoist is properly engaged and if the Hoist switch is closed (or if any external interlock device is
remained open)
EXTERNAL CONTROLS
Refer to the wiring diagram on page 20 before connecting power or any external device to the ECB. Neglecting
to use the proper terminals will result in complete damage to the ECB. If you are not certain about procedures,
please consult Manaras for assistance.
NOTE: Do not attempt correction by reversing wires on control station.
L.E.D
Color
STATUS
+24 V
Green
When ON indicates the presence of 24VDC on the Logic Board
+5 V
Green
When ON indicates the presence of 5VDC power in the Control Circuit
Open Limit
Red
When ON indicates door position, completely open.
Open
Red
Only when the
open relay
is activated (open relay is energized)
Close Limit
Red
When ON indicates door position, completely close.
Close
Red
Only when the
close relay
is activated (close relay is energized)
Safe
Red
Light ON only when safety devices are activated.
INDICAT
(Wrong
Handling)**
Red
Flashes only when motor runs in opposite direction and activates the
wrong limit switch.
Stay ON only when the “centrifugal switch” is opened
(please contact
technical support)
STOP
Yellow
In normal conditions light; stay ON, goes OFF every time when press
STOP button or hoist is engaged
WARNING
WHEN REPLACING AN ELECTRONIC CONTROL BOARD DO CHECK THAT ALL JUMPERS ARE
POSITIONED AS INDICATED IN THE WIRING DIAGRAMS ON PAGE 27 FOR SINGLE PHASE AND
ON PAGE 28 FOR 3-PHASE
.
Summary of Contents for Opera-GH
Page 18: ...18 6 Opera GH exploded view...
Page 29: ...29 7 10 Single phase ECB wiring diagram...
Page 30: ...30 7 11 3 Phase ECB wiring diagram...
Page 42: ...42 9 9 Single phase Hardwired wiring diagram...
Page 43: ...43 9 10 3 phase Hardwired wiring 10 3 phase Hardwired wiring diagram...
Page 45: ...45 NOTES...
Page 46: ...46 NOTES...
Page 47: ...47 NOTES...
Page 48: ...48 BOOK146 REV 1 2007 02 19...