11. TROUBLE SHOOTING

 

 

 

Problem

 

 

Reason

 

 

Solution Offer

 

 

 
 
Reductor doesn't work 
 There is  

H4

 warning  on 

control panel digital screen

 

 

 

Electricity connection might be loose

 

Check the connection 
Tighten the klemens 
cables.

 

Shaft  from the reductors can be 
congested

 

Clean up the shaft bearing 
helezon entrance hole 

 

 

check the fuel congestion  led.

 

If it doens't work call service.  
Push ON-OFF button 2 seconds.

 

 

Motor  can be broken 

 

 

Call service.

 

Reductor runs but fuel can 
not reach to burning cell

 

 

 

Bunker – fuel tank connection can be 
blocked 

 

 

Fuel should be pour from a 
siever and dry fuel should be 
burned.

 

 

 
 
Burning efficiency is low

 

 

Fuel is not well quality

 

Use high quality, dry and 
proper size fuel.

 

Boiler settings are not made according 
to the fuel type.

 

 
Make the proper settings from table 
1

 

 

Chimney draught is weak.

 

 

Chimney should be cleaned up.

 

  There is 

H2 warning 

on control    panel 
digital screen.

 

Heat sensor or card can be broken.

 

 

Call service

 

 

 
 
Smoke comes from chimney 
connections

 

 Air holes which are inside the 
boiler, can be blocked.

 

Clean up holes and smoke pipes 
regularly

 

Boiler  Chimney connections can be 
loosen

 

Check the boiler chimney 
exit and pipe connections.

 

 

Chimney draught is weak.

 

 

Clean up the chimney.

 

 

 
 
 
 
Fan doesn't run

 

 

Set termostat 
temperature    

 is 

achieved

 

 Fan stops running when the 
boiler water catches up the set 
termostat temperature. When 
temperature decreases 5 
degrees it starts running again.

 

 

Fuel can be finished

 

 

Make fuel loading.

 

 

Fan button can be off.

 

 

Open main fan button.

 

 
 

There is H3 
warning on control 
panel digital screen. 

 

 
 
 

 Boiler water temperature is very high

 

Check the  water in boiler. If it 

is inadequate, complement.

 

 Circulation pump is congested

 

Boiler valves can be off

 

There is air in system and 

there is no circulation. Purge 
the air.

 

 
 

 

H1 warning on 

control panel digital 
screen 

 

 

 No fuel or  fuel might be congested.

 

   
  *Check the fuel in stocker. 
Complete  the fuel if it is inadequate 
and carry out the procedure in first 
use. 
 * Fuel was wet when poured inside 
the stocker, it is now stucked and 
can not be loaded. Fuel is pumped 
down by applying pressure with an 
object.

 

 

 

                                                     

Summary of Contents for 25 MKK-S

Page 1: ...1...

Page 2: ...TION AND WATER FLOOD 9 BOILER INSTALLATION SCHEMA 10 4 2 AIR CONNECTION 11 4 3 CHIMNEY 11 CHIMNEY CONNECTION SCHEMA 12 5 TECHICAL FEATURES 13 6 CONTROL PANEL 14 7 FIRST OPEATION AND USE 15 7 1 FIRST B...

Page 3: ...y and World market Our company which has acquired advanced technology and superior quality stands on in accordance with these principles This handbook is a helpful guide during operation and maintenan...

Page 4: ...strictly forbidden Please do not operate the boiler without water Do not feed cold water to hot boiler If for any reason the boiler temprature is over 90 degrees do not attempt to feed cold water to t...

Page 5: ...g and waiting time on the electronic control panel Detoriations as a result of burning are minimised thanks to cast iron burning bunker Fan with quiet running cycle period and clap ensures maximum eff...

Page 6: ...6 3 SECTIONS OF THE BOILER See techic table for dimensions stated with letters 5 6...

Page 7: ...r must be connected to a good drawing chimney and minimum number of elbows should be used between chimney and boiler Boiler must be placed at a location with enough air intake for an efificient burnin...

Page 8: ...om one end of the pipes and to drain off at the other side Circulation pump must be installed on boiler water return pipe During installation there must be enough working space left for technical serv...

Page 9: ...n of hot water must be provided by natural circulation The diameter of the pipe to be used at by pass line should be the same diameter size with the pipe used in installation at minimum As an extra se...

Page 10: ...10 BOILER INSTALLATION SCHEMA...

Page 11: ...ertical length must not be shorter than 60 cm and longer than 2 meters and pipe must be connected to the chimney with minimum 10 degree of angle We suggest not to use enamel stove pipes as it creates...

Page 12: ...the building if the chimney must pass from outside the isolation must be done properly The chimney must be frequently cleaned in order to avoid tar and soot and clogs Please avoid foreign objects cem...

Page 13: ...13 5 TECHNICAL SPECIFICATION...

Page 14: ...r fuel loading 04 255 sec Fuel feeding period setting button Sets fuel loading period 04 60 sec Fan Setting Button Sets speed level of fan From 1 to 5 Thermostat Setting Button Adjust the intended tem...

Page 15: ...iler lids must be closed and fan must be runned in low speed until the coal is completely combusted If fan blows too much air big slinders occurr because of the cooling effect of burning tank Make the...

Page 16: ...ses 5 C below set degree Running and stopping of circulation pump and fan can be monitored from flashing leds on digital indicator on control panel Circulation pump will run automatically for 3 second...

Page 17: ...nclogged Air holes must be cleaned up by turning on the fan for 15 minutes Electricity connection must be cut off before the maintainance Please ventilate the area before cleaning the boiler Electrici...

Page 18: ...18 10 ELECTRICITY SCHEMA...

Page 19: ...e comes from chimney connections Air holes which are inside the boiler can be blocked Clean up holes and smoke pipes regularly Boiler Chimney connections can be loosen Check the boiler chimney exit an...

Page 20: ...use of the supporting ring When the boiler is lifted up with crane there shouldn t any living being under the boiler Boiler must be carried with its accessories installed on it B CARRYING BOILER ON VE...

Reviews: