BOXER SERIES 80-120 KVA
EXPLANATIONS OF LOGGING
AG-SD-37/ Publication Date: 19.10.2012/Rev. No:1/Rev. Date:16.11.2012
50
60
Maintenance
Bypass Mode
UPS is operating in the maintenance bypass mode, loads are
energized through maintenance bypass line.
61
Parallel Mode
2 or more UPS are operating in power sharing mode. Load is fed
through UPSs’ inverter lines.
62
Test
Mode
UPS has switched to battery test mode, loads are energized through
rectifier- battery- inverter line as source sharing.
63
Switch to
Inverter Mode
Switching to inverter mode command has been given via front
panel.
64
Output Voltage
Error
Output voltage is detected during the period of starting UPS. UPS
has been stopped.
65
PFC Stop
Command
Abnormal situation is detected during the moment of rectifier
operating. UPS has given a command to stop itself.
66
Start Command
Start command is given via UPS command menu.
67
Stop Command
Stop command is given via UPS command menu.
68
UPS Stopped
UPS has been stopped.
69
Bypass
Error
UPS has switched to bypass mode so many times in a short period,
UPS will be shut down.
70
Parameters
Changed
Device-related parameters were changed on the service menu.
71
Battery Changed
Battery replacement date has been changed. Battery statistics will
be reset.
72
Load Impact
Transfer
The load which cannot be handled by inverter is activated. Loads
will be transferred to bypass line.
73
Parallel Command
An UPS which is operating in parallel mode has been given a
command to change the status of static switches.
74
No Parallel CAN
Bus
Communication
Slave UPS which is operating in parallel mode can’t reach to master
UPS from CAN bus. If UPS is operating, will be shut down.
75
Externally Start
Command
UPS which is operating in parallel mode has been received a
command to start up by another UPS.
76
Externally Stop
Command
UPS which is operating in parallel mode has been received a
command to stop by another UPS.
77
Externally Switch
To BYPASS.
UPS which is operating in parallel mode has been received a
command to transfer the load to bypass line.
78
Externally Switch
To UPS
UPS which is operating in parallel mode has been received a
command to transfer the load to inverter.
79
Parallel
Communication
FE Error
Slave UPS which is operating in parallel mode has detected a failure
of input current sharing.
80
Inverter OKEY
Inverter voltage reached needed value after UPS is started up. UPS
can feed the loads through inverter.
81
Abnormal
Battery
Temperature
Battery temperature is out of defined limits, batteries can be
damaged.
82
EPO key pressed
EPO button is pressed.