BOXER SERIES 80-120 KVA
PRODUCT DESCRIPTION
AG-SD-37/ Publication Date: 19.10.2012/Rev. No:1/Rev. Date:16.11.2012
13
2.3.1 Advanced Level Functions (Automatic Battery Test)
The auto battery test automatically discharges 10% of the battery existing capacity in a certain
period defined (default is 90 days). The period between two tests can be adjusted by user
between 30-360 days. At the end of the test, one of these two status, “
good or replace
” is
determined.
At the end of this test, if batteries are reported as
“replace”
, then the batteries
are completely drained after the test. In this case, loads can remain unpowered in
case of mains power off.
This test can be automatically started by command from front panel, via telnet interface, via
RS232 smart communication or via MakNET (SNMP, see the options).
As a result of all these tests, it is checked whether the batteries that are presently used can
supply the minimum needs of loads in case of the first power-off or not. It is recommended that
test results be checked at regular intervals.