BOXER SERIES 80-120 KVA
OPERATION
AG-SD-37/ Publication Date: 19.10.2012/Rev. No:1/Rev. Date:16.11.2012
43
4.1.3.4 Switching from Normal Mode to Maintenance Bypass Mode
Make sure that the inverter output is synchronous with the
maintenance bypass line before switching to maintenance bypass
mode. Otherwise, there is a possibility of cutting off the load power
for a short while.
NOTICE! When device is fed through the maintenance bypass mode,
no separateneutral connection is used, so the neutral connections
must not be disconnected at any point inside the device. Otherwise,
the neutral connection to the load will be interrupted. In such a case
critical loads may remain without energy.
Switch the device to static bypass mode using the front panel. Check if static bypass led has
flashed in mimic diagram.
Main Menu>Control> Switch to BYPASS