BOXER SERIES 80-120 KVA
OPERATION
AG-SD-37/ Publication Date: 19.10.2012/Rev. No:1/Rev. Date:16.11.2012
40
5. Check the device has switched to normal operation mode, via
front panel display LEDs and LCD panel.
6. Switch battery circuit breaker (CB4) to ON position.
7. Switch output circuit breaker (CB3) to ON position.
8. You can turn on the loads connected to the device.
After all these steps, check that load is fed through inverter static switches via mimic diagram. In
a contrary situation, check UPS total and phase loads. The UPS gives audio alerts in an overload
condition, without feeding critical AC loads.