BOXER SERIES 80-120 KVA
PRODUCT DESCRIPTION
AG-SD-37/ Publication Date: 19.10.2012/Rev. No:1/Rev. Date:16.11.2012
17
2.4.4 Password Protected Menus
Some menus such as the control menu are password
protected. To enter password choose each digit with
UP/DOWN
buttons and confirm with
ENT
button.
User level password is: 0000
2.4.5 Control Menu
The followings can be done in the control menu:
Start
Start the UPS.
Stop
Stop the UPS.
Switch to BYPASS
Switch to static BYPASS mode.
Switch to UPS
Switch to online mode.
Bat. Quick Test
Start the quick battery test.
Bat. Capacity Test
Start the deep battery test.
Stop Battery Test
Stop the battery test.
Battery status test, drains the 10% of battery energy and reports batteries which has more
capacity than 10% as
“Good”
, less capacity than 10% as
“Replace”
according to the test results.
After the device is started and every 24 hours, it automatically performs a quick battery test, if
test counter value is zero.
Batteries must be fully charged and kept in floating situation for 5 hour before performing the
battery status test.