CHALLENGER SERIES 80‐120 KVA
SAFETY AND WARNINGS
AG‐SD‐36 Rev. No:0 Rev. Date:15.11.2012 Publish No:1
Fire extinguishing equipment must be kept nearby the UPS.
1.2.
Clearance
and
Access
Clearance
There is no any air inlet or outlet grill on the left or right sides of our 80‐120 kVA UPS. All air goes
in to UPS from the front and is evacuated from the rear through fans. There must be spaces at
least 1 meter at the front side of UPS. Should not be permanent or temporary use within the limits
specified. Otherwise, the UPS performance will decrease.
Access
Operator reaches UPS via front panel on 80‐120 kVA UPS. Therefore, enough area must be left for
operator.. There is no limit to the sides of the device.
1.3.
Storage
UPS should be kept in a room or area where is protected from excessive moisture and heat before
commissioning.
WARNING:
Unused batteries must be charged at regular intervals. This time interval is determined by the
battery supplier. Charging can be performed periodically by connecting to a proper mains for a
while.
1.4.
Shipment
Carrying vehicles must have enough features and characteristics to carry UPS.
Be more careful of sudden movements, especially when batteries are inside of cabinet.
Move the UPS as rarely as possible.