CHALLENGER SERIES 80‐120 KVA
PRODUCT DESCRIPTION
AG‐SD‐36 Rev. No:0 Rev. Date:15.11.2012 Publish No:1
Battery status test, drains the 30% of battery energy and reports batteries which has more
capacity than 15‐30% as
“Good”
, less capacity than 15% as
“Replace”
according to the test
results.
After UPS is started and every 24 hours, it makes a quick battery test ,if test counter value is zero
(0).
Note
: Batteries must have been fully charged and kept in floating situation for at least one hour
before performing the quick battery test.
Status on the System
>
Battery
>
Remaining
Time
can
be
seen
.
If “
Stop
Battery
Test
” is chosen from the menu, the UPS cancels the battery test and goes back to
the previous operating state.
2.4.6.
Status
Menu
Mains Output, Bypass, Battery, Temperatures, inverter, Alarms and UPS information can be seen
on this menu.