CHALLENGER SERIES 80‐120 KVA
INSTALLATION
AG‐SD‐36 Rev. No:0 Rev. Date:15.11.2012 Publish No:1
11.
Please check that whether there is appropriate battery voltage on the input terminals of the
battery of UPS by measurement tool.
The external battery cable selection is determined by the application. Recommended fuses are
given for UPS and battery cabinet. The lowest diameter cable that can be connected to those fuses
is recommended to be used. Please, refer to standard called EN 50525‐2‐31(VDE 0100‐430) in
this subject. Bu konuda EN 50525‐2‐31(VDE 0100‐430) adlı standardı referans alınız. selection
should be such that the cable will allow at most 0.5 Vdc decreasing.
“
External Battery Temperature Measurement Kit
” which is sold as optional is recommended to
purchase for optimization according to battery temperatures on the external battery cabinets
applications. Otherwise, your batteries will not be optimized according to temperatures.
CH80120EN17R0