CHALLENGER SERIES 80‐120 KVA
TECHNICAL SPECIFICATIONS
AG‐SD‐36 Rev. No:0 Rev. Date:15.11.2012 Publish No:1
6
Technical
Specifications
Technical
Specifications
Power
80KVA
100KVA
120KVA
Active
Power
64kW
80kW
96kW
Input
Input
Voltage
Range
220 ± %15 (L‐N) or 380 ± %15 (L‐L) 3P + N + PE
Input
Power
Factor
At Full Load > 0,99
Input
Frequency
Range
50Hz ± 10% / 60Hz ± 10% (Adjustable)
Rectifier
IGBT Rectifier
Total
Harmonic
Distortion
(THDi)
<%5
Output
Output
Voltage
Range
220/380 VAC (230/400 VAC adjustable) 3P + N ± 1% Static, ± 1%
Dynamic
Recovery
At 0% ‐ 100% ‐ 0% load, maximum output tolerance %5, %1 Back to band
<40ms
Efficiency
Up to %93
Output
Frequency
Range
synchronous with the network
at the range of 50Hz ±2% , mains when
is out of range 50Hz
± 0,2%, battery mode 50Hz ± 0,2%
Output
THD
(THDv)
Lineer <%3
Non‐Lineer <%4
Crest
Factor
(CF)
3:1
Overload
Capacity
At %125 load 10 min. , at %150 load 1 min.
Protections
The input voltage is out of tolerance, input frequency is out of tolerance,
input phase failure, output voltage is out of tolerance, output frequency is
out of tolerance, output phase failure, DC component that can occur at the
output voltage, Overload that will occur at the output (out of the periods
specified), Overheating that will cause failure related to over temperature,
high voltage which will occur at DC Bus voltage, low voltage which will
occur at DC Bus voltage, short circuit at the output.
Battery
Quantity
(12V
DC
VRLA)
50
Charge
Value
(
C
)
Nominal 0.1 C, adjustable.
Battery
Power
25% of the device power
Communnication