CHALLENGER SERIES 80‐120 KVA
EXPLANATIONS OF LOGGING
AG‐SD‐36 Rev. No:0 Rev. Date:15.11.2012 Publish No:1
5
Explanations
of
Logging
UPS will beep when any problem is detected. You can see the first information about the situation on
the front monitor panel. This may not be enough most of the time. In this case, you can see the
following warnings by using log screen.
Warning
Warning
Description
1
RS232
Start
Command
UPS was started by RS232 communication software.
2
RS232
Stop
Command
UPS was stopped by RS232 communication software.
3
Auto
Restart
After the batteries discharge totally, UPS restarted itself automatically
after the mean time which adjusted that follows the mains getting back
4
UPS
Startup
The main board of the UPS is energized.
5
Soft
Start
Fail
UPS could not ramp the DC bus up.
6
Quick
Battery
Test
Quick battery test has began.
7
Deep
Battery
Test
Battery capacity test has began.
8
Battery
Self
Test
Periodical battery test has began.
9
End
Of
Discharge
Batteries’ voltage has gone below cut off voltage value while UPS was
operating on the battery mode.
10
Overload
Timeout
UPS has operated at overload more than time limit adjusted. The Loads
will be transferred to bypass line.
11
End
of
Battery
Test
Battery test has completed. You can see the all results via front panel
status menu.
12
Batt.
Test
Aborted
Test was aborted manually or by UPS since the criterias were not
provided during battery test.
13
Manuel
Switch
To
BYP
Static switchs directions were changed manually to the bypass line via
UPS command menu.