CHALLENGER SERIES 80‐120 KVA
EXPLANATIONS OF LOGGING
AG‐SD‐36 Rev. No:0 Rev. Date:15.11.2012 Publish No:1
62
Bypass
Mode
UPS is operating in the bypass mode, load are energized through
bypass line.
63
Maintenance
Bypass
Mode
UPS is operating in the bypass mode, load are energized through
bypass line.
64
Parallel
Mode
2 or more UPS are operating in power sharing mode. Load is fed
through UPSs’ inverter lines.
65
Test
Mode
UPS has switched to battery test mode, loads are energized through
rectifier‐ battery‐ inverter line as source sharing.
66
EKO
Mod
KGK eko moddan çalışıyor. Yükler bypass hattı üzerinden besleniyor.
67
Switch
to
Inverter
Command
The direction of the static switches was varied manually on the rectifier
through UPS commands menu.
68
Output
Voltage
Error
Output voltage is detected during the period of starting UPS . UPS has
been stopped.
69
PFC
Stop
Cmd.
Abnormal stuation is detected during the moment of rectifier
operating.UPS has stopped itself.
70
Manuel
Start
Command
Start command is given via UPS command menu.
71
Manuel
Stop
Command
Stop command is given via UPS command menu.
72
Batt.
Swtch.
Failure
An error occurred while ramping up the battery bus, Batteries could
not be activated.
73
UPS
Stopped
UPS has been stopped.
74
Bypass
Problem
UPS has switched to bypass mode so many times i a short period, UPS
will be shut down.
75
Parameters
Changed
Device‐related parameters were changed on the service menu
76
Batterys
Changed
Battery replacement date has been changed. Battery statistics will be
reset.
77
Battery
Contactor
OFF
Battery mechanical switch on the service menu was deactivated.
Batteries are not active.
78
Battery
Contactor
ON
Battery mechanical switch on the service menu was activated. Batteries
are active.