CHALLENGER SERIES 80‐120 KVA
EXPLANATIONS OF LOGGING
AG‐SD‐36 Rev. No:0 Rev. Date:15.11.2012 Publish No:1
96
Fan
Failure
Unable to communicate with the fan control system. Only for UPSs that
contain the fan control system.
97
Output
DC
Volt.
Fault
Over Inverter DC voltage. Loads will be transferred to the bypass line.
98
Battery
Temp.
Nor.
Battery temperature is normal.
99
Output
Signal
ON
UPS output switch is opened. Loads can be energized.
100
Fans
Active
Able to communicate with the fan control system. Only for UPSs that
contain the fan control system.
101
PFC
Pbus
OverVoltage
Positive DC Bus overvoltage.
102
PFC
Nbus
OverVoltage
Negatif DC Bus overvoltage
103
PFC
PhL1
OverCurrent
Short circuit protection is activated for rectifier L1 phase.
104
PFC
PhL2
OverCurrent
Short circuit protection is activated for rectifier L2 phase.
105
PFC
PhL3
OverCurrent
Short circuit protection is activated for rectifier L3 phase.
106
Single
Stop
Command to stop itself has been given to UPS which is operating in
paralel mode separately from paralel system.
107
Master
Changed
UPS became master device in paralel system.
108
Par.
Bus
ID
Collision
ID value of one or more UPS is the same as each other in parallel
system.
109
Output
Offset
Err.
One or more phase of slave UPS’ output is not connected to master UPS
in Parallel systems.
110
Bypass
Short
Circuit
Short‐circuit current limit has been exceeded in the maintenance
bypass mode. UPS is shut down.
111
RMS
output
Failure
The value of output voltage is out of the limits. UPS will be shut down.
112
Stop
All
Units
Stop all units command was given via front panel.
113
Float
Charge
Mode
UPS charge mode has switched to the standby mode at the constant
voltage from constant current mode.