Ventilation and air extraction take place for 

roughly 10 minutes. Then the fan is switched 

off for a further 10 minutes so that the moist 

room air can mix with the dry air brought in 

from outside (passive time). After the waiting 

period has lapsed, the comparison of the 

inside and outside humidity is repeated.  
If the absolute humidity of the outside air is 

found to be greater than that of the air inside 

the room (aH

outer

 > aH

inner

), air is not 

exchanged. This prevents moist air from 

flowing in. The fan is only switched on again 

once the climate conditions make 

dehumidification possible. 

 

Button 1 

(Taster 1) 

Reference value 

determination

 

Button 2 

(Taster 2) 

Manual ventilation  

LED 1 

Operating mode 

LED 2 

Dehumidification status 

 

Display

 

Function

 

LED 1: On 

Automatic operating mode  

LED 1: Blinking* 

Manual ventilation  

LED 1: Blinks 

twice with long 

pause 

Frost protection 

LED 1: Blinks 

three times with 

long pause 

Protection against 

insufficient humidity 

LED 2:  

On (in automatic 

mode) 

Active time during 

dehumidification 

(Fan on) 

LED 2: Off 

Passive time during 

dehumidification 

(Fan off) 

LED 2 
Blinking* 

Successful 

dehumidification achieved 

(resettable with button 1) 

 

* Simultaneous blinking: 

Blinking of LED 1 or LED 2 indicates an 

operating mode or function. If both LEDs blink 

simultaneously, there is a fault. See chapter 

Fault rectification. 

 

Successful dehumidification –  

Button 1 / Blinking LED 2: 

  

In the case that the room humidity is reduced 

by at least 0.2 g/m

3

, in comparison to the 

reference value, the AKE 150 signals 

successful dehumidification by LED 2 

blinking. A reference value of 9 g/m

3

 is set 

on-site. A new reference value can be set at 

any time by pushing button 1 during ongoing 

operation. Saving of the new reference value 

is confirmed by the LED 2 blinking briefly. 

 

Frost protection:

 

To prevent the room from cooling down, the 

AKE 150 has a frost protection function. This 

means that the fan automatically switches  

off at inside room temperatures of less than  

5 °C. 

 

Protection against insufficient humidity: 

For reasons of health protection and energy 

efficiency, the AKE 150 offers a protection 

against insufficient humidity function. This 

protective function ensures the switching off 

of the fan if a relative humidity of less than  

30 % is reached. 

 

Manual ventilation – Button 2:  

The AKE 150 switches the fan on and off 

automatically and in a manner optimised to 

demand. When off, the fan can be switched 

on manually with button 2 and manual 

ventilation therefore takes place. Manual 

operation is ended by again pressing button 2 

or automatically after approximately  

20 minutes. 

Summary of Contents for AKE 150

Page 1: ...ung Automatische Kellerentfeuchtung Mounting and operating instructions Automatic cellar dehumidification Notice de montage et mode d emploi D shumidification automatique des caves AKE 150 www m aico...

Page 2: ...ische Daten 6 6 Sicherheitshinweise 6 7 Montagevorbereitungen 7 7 1 Wand 7 7 2 Decke 7 7 3 Rohr 7 7 4 Au enabdeckung 7 7 5 Ventilator 8 8 Montage 9 8 1 Einbau Au enverschlussklappe mit Au enklima Sens...

Page 3: ...1 Ger te bersicht Abb A 1 Geh use mit Motor 2 Fl gelrad 3 Designabdeckung 4 Abdeckung 5 Innengitter 6 Innen Klimasensor 7 Elektronikabdeckung 8 Elektronikplatine 9 Leitungst lle Unterputzanschluss 10...

Page 4: ...assivzeit bei der Entfeuchtung Ventilator aus LED 2 Blinkend Entfeuchtungserfolg erreicht mit Taste 1 r cksetzbar Gleichzeitiges Blinken Ein Blinken von LED 1 oder LED 2 entspricht einer Betriebsart b...

Page 5: ...Au enbedin gungen zu einer Raumbefeuch tung f hren Daher ist unbedingt bei Verwendung eines externen Schalters auf die Dauer des L ften zu achten 3 3 Bestimmungsgem e Verwendung Dieses Ger t ist auss...

Page 6: ...chtung zur Trennung vom Netz mit mind 3 mm Kontakt ffnung je Pol erforderlich Ger t nur mit auf Typenschild angegebener Spannung und Frequenz betreiben Keine Ver nderungen am Ger t vornehmen Ger t nie...

Page 7: ...2 Wanddurchbruch anbringen oder Kernloch bohren Mindestdurchmesser 150 mm Empfehlung Wandh lse WH 150 einbauen Wanddurchbruch mit Mindestdurchmesser 170 mm anbringen 3 Netzleitung bis an den Montageo...

Page 8: ...einlegen 3 Beigef gtes Dichtband am Stutzen mittig anbringen 7 5 Ventilator 1 Ger t auspacken und Abdeckungseinheit 3 4 abnehmen Zum L sen der Abdeckung Rasthaken Pfeil mit Schraubendreher entriegeln...

Page 9: ...anschluss Leitungst lle 9 im Geh use belassen und Leitungst lle 10 aus dem Geh use nehmen ACHTUNG Kurzschlussgefahr und Ger tebesch digung Eindringen des Wasser bei falscher Ein f hrung der Netzleitun...

Page 10: ...10 mm abisolieren 2 Netzleitung an Federklemme 13 gem Anschlussschaltbild 14 elektrisch anschlie en siehe auch Schaltbild in Kapitel 13 3 Sitz der Leitungst lle 9 kontrollieren Diese muss gut abdichte...

Page 11: ...3 diese gleichm ig parallel von Abdeckung 4 abziehen und mit Wasser reinigen 3 Designabdeckung 3 anbringen Darauf achten dass die 4 Zapfen richtig in Abdeckung 4 einrasten 4 Netzsicherung einschalten...

Page 12: ...lten 2 Abdeckungen 3 und 4 abnehmen 3 Elektronikabdeckung 7 entfernen 4 Netzleitung entfernen 5 Ventilator ausbauen 13 Entsorgung Nicht in den Restm ll Das Ger t enth lt teils wiederver wertbare Stoff...

Page 13: ...Duct 18 7 4 External cover 18 7 5 Fan 18 8 Mounting 19 8 1 Installation of external shutter with outdoor climate sensor 19 8 2 Fan housing installation 19 8 3 Electrical connection 20 8 4 Final assem...

Page 14: ...rnal grille 6 Internal climate sensor 7 Electronics cover 8 Electronic circuit board 9 Cable grommet recessed mounted connection 10 Cable grommet surface mounted connection 11 External climate sensor...

Page 15: ...ing Blinking of LED 1 or LED 2 indicates an operating mode or function If both LEDs blink simultaneously there is a fault See chapter Fault rectification Successful dehumidification Button 1 Blinking...

Page 16: ...orage rooms showrooms offices changing rooms and similar rooms up to a floor area of approximately 70 m2 Operation is only permitted with a fixed installation within buildings installation on walls or...

Page 17: ...y caused by objects in the impeller Do not insert any objects in the unit Danger of injury from rotating impeller Do not get too close to the fan unit to avoid hair clothing or jewellery being drawn i...

Page 18: ...ation builds up in the fan housing Thermally insulate ventilation ducts in a professional manner Allow for a condensation drain or condensate collector in the riser Perform installation preparations a...

Page 19: ...ter with outdoor climate sensor 1 Guide sensor connection cable 11 through the wall breakthrough wall sleeve and pull it through to the other side of the brickwork For the connection to the control el...

Page 20: ...cable sheathing completely and does not penetrate too far into the connecting area 6 Lead sensor connection cable from the external climate sensor 11 into the hole provided arrow in the fan housing 1...

Page 21: ...tor sockets 3 Fit cover 4 8 5 Start up 1 Switch the mains fuse on 2 Run function test 3 Save reference humidity by pushing button 1 15 4 Fit designer cover 3 Saving of the reference values is shown by...

Page 22: ...or is interrupted Check the sensor connection cable and plug contact Both LEDs blink in three second intervals Internal climate sensor error The internal climate sensor has not been detected Check for...

Page 23: ...1 Mur 28 7 2 Plafond 28 7 3 Gaine ronde 29 7 4 Protection externe 29 7 5 Ventilateur 29 8 Montage 30 8 1 Montage du volet de fermeture ext rieur avec d tecteur de temp rature ext rieure 30 8 2 Montag...

Page 24: ...dant 1 Marche suivre Suivez les instructions dans l ordre indiqu 3 Informations produit 3 1 Vue d ensemble de l appareil Fig A 1 Bo tier avec moteur 2 H lice 3 Cache de protection design 4 Cache de pr...

Page 25: ...le LED 1 2x clig notements avec longue pause Protection contre le gel LED 1 3x clig notements avec longue pause Protection contre l air sec LED 2 Marche en mode automatique P riode active de d shumidi...

Page 26: ...pteur Une coupure automatique du mode manuel est exclue dans ce cas La ventilation manuelle est galement possible pendant la protection contre le gel et contre l air sec ATTENTION Endommagement de la...

Page 27: ...de s curit G n ralit s Montage et branchement lectrique doivent exclusivement tre effectu s par des sp cialistes selon les instructions du chapitre 2 Lire attentivement le pr sent mode d emploi avant...

Page 28: ...bre d au moins 150 cm p ex d une grille de ventilation de porte MLK 7 Pr paratifs de montage 7 1 Mur Respecter les distances minimum prescrites par rapport au mur et au plafond selon la figure 1 Assur...

Page 29: ...u bo tier 2 Poser le c ble de d tecteur au centre de la tubulure 3 Poser le ruban isolant fourni au centre de la tubulure 7 5 Ventilateur 1 D baller l appareil et retirer le cache de protection 3 4 Po...

Page 30: ...es M6 de 6 mm et y introduire les chevilles 4 Pousser avec pr caution le manchon de c ble 9 hors du bo tier et le sortir Pour effectuer un raccordement lectrique apparent il est galement possible de l...

Page 31: ...ser que des conducteurs individuels dans l appareil Pour ce faire d nuder le c ble secteur sur une longueur de 110 mm Isoler les conducteurs individuels sur 9 10 mm 2 Brancher lectriquement le c ble s...

Page 32: ...a valeur de r f rence est signal e par le clignotement de la LED 1 9 Entretien L appareil ne n cessite aucun entretien 10 Nettoyage DANGER Danger de mort par lectrocution D sactiver le fusible secteur...